OPERATION
6
65
SMARTLINE® RM60 (FMCW)
www.honeywell.com/ps
34-VF-25-31 iss.4 GLO December 15 US
•
Blocking Distance (C.1.9)
Use the flange facing as the reference point for the 4 and 20 mA current output settings. The 4
and 20 mA current output settings are the minimum and maximum points of the measurement
scale.
You can change the reference point from which distance is measured. Use this menu
item:
•
Reference Offset (C.1.10)
For more data about the menu items, refer to
Function description
on page 53, table C. Advanced
setup.
6.4.5 Level measurement
The device displays level measurements when an output is set to level.
INFORMATION!
If you move the reference point above the flange, add this value when you give a distance for the
4 and 20 mA current output settings. If you move the reference point below the flange, subtract
this value when you give a distance for the 4 and 20 mA current output settings.
CAUTION!
If the distance for 4 mA is set in the blocking distance, the device will not be able to use the full
current output range.
Figure 6-4: Distance measurement
1
Tank Height (C.1.2)
2
Reference Offset (C.1.10)
3
Blocking Distance (C.1.9)
4
4 mA Setting (C.3.2 or C.4.2)
5
20 mA Setting (C.3.3 or C.4.3)
6
Maximum effective measuring range
7
Non-measurement zone
Summary of Contents for SmartLine RM60
Page 8: ...CONTENTS 8 www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US SMARTLINE RM60 FMCW ...
Page 76: ...6 OPERATION 76 SMARTLINE RM60 FMCW www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US ...
Page 86: ...7 SERVICE 86 SMARTLINE RM60 FMCW www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US ...
Page 126: ...10 APPENDIX 126 SMARTLINE RM60 FMCW www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US ...
Page 127: ...APPENDIX 10 127 SMARTLINE RM60 FMCW www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US ...