6
OPERATION
66
SMARTLINE® RM60 (FMCW)
www.honeywell.com/ps
34-VF-25-31 iss.4 GLO December 15 US
Menu items related to level measurement are:
•
Output Function (C.3.1 or C.4.1)
•
Tank Height (C.1.2)
•
Blocking Distance (C.1.9)
Use the silo bottom as the reference point for the 4 and 20 mA current output settings. The 4 and
20 mA current output settings are the minimum and maximum points of the measurement scale.
You can change the reference point from which level is measured. Use this menu item:
•
Tank Bottom Offset (C.1.11)
For more data about the menu items, refer to
Function description
on page 53, table C. Advanced
setup.
INFORMATION!
If you move the tank bottom offset below the silo bottom, add this value when you give a level for
the 4 and 20 mA current output settings. If you move the tank bottom offset above the silo
bottom, subtract this value when you give a level for the 4 and 20 mA current output settings.
CAUTION!
If the level for the 20 mA is set in the blocking distance, the device will not be able to use the full
current output range.
Figure 6-5: Level measurement
1
Tank Bottom Offset (C.1.11)
2
Tank Height (C.1.2)
3
Blocking Distance (C.1.9)
4
Maximum effective measuring range
5
20 mA Setting (C.3.3 or C.4.3)
6
4 mA Setting (C.3.2 or C.4.2)
7
Non-measurement zone
Summary of Contents for SmartLine RM60
Page 8: ...CONTENTS 8 www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US SMARTLINE RM60 FMCW ...
Page 76: ...6 OPERATION 76 SMARTLINE RM60 FMCW www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US ...
Page 86: ...7 SERVICE 86 SMARTLINE RM60 FMCW www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US ...
Page 126: ...10 APPENDIX 126 SMARTLINE RM60 FMCW www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US ...
Page 127: ...APPENDIX 10 127 SMARTLINE RM60 FMCW www honeywell com ps 34 VF 25 31 iss 4 GLO December 15 US ...