Honeywell
Parameter Descriptions 53
9
2.5 L
OCAL
/R
EMOTE
This parameter defines whether the control place of the drive is remote (I/O or
FieldBus) or Keypad. Keypad can also be selected as control place by press-
ing the navigation wheel for 5 seconds.
The priority order of selecting control place is
1. Navigation wheel
2. Forced from I/O
3. Parameter 2.1
9.3 FREQUENCY REFERENCES (CONTROL PANEL: MENU PAR -> P3)
3.3 I/O
REFERENCE
Defines the selected frequency reference source when the drive is controlled
from the I/O terminal.
0 =
Preset speed 0 - 7
1 =
Keypad reference
2 =
Reference from Fieldbus (FBSpeedReference)
3 =
AI1 reference (terminals 2 and 3, e.g. potentiometer)
4 =
AI2 reference (terminal 4 and 5, e.g. transducer)
3.4 - 3.11 P
RESET
SPEEDS
0 - 7
These parameters can be used to determine frequency references that are ap-
plied when appropriate combinations of digital inputs are activated. Preset
speeds can be activated from digital inputs despite of the active control place.
Parameter values are automatically limited between the minimum and maxi-
mum frequencies. (par. 3.1, 3.2).
Speed
Preset speed B2 Preset speed B1
Preset speed B0
If P3.3 = 0, Preset speed 0
Preset speed 1
x
Preset speed 2
x
Preset speed 3
x
x
Preset speed 4
x
Preset speed 5
x
x
Preset speed 6
x
x
Preset speed 7
x
x
x
Table 9.1: Preset speeds 1 - 7