Honeywell
Parameters 39
8
8.5 RAMPS AND BRAKES SETUP (CONTROL PANEL: MENU PAR -> P4)
8.6 DIGITAL INPUTS (CONTROL PANEL: MENU PAR -> P5)
Code
Parameter
Min
Max
Unit Default
ID
Note
P4.1
0,0
10,0
s
0,0
500
0
= Linear
>0
= S-curve ramp time
P4.2
Acceleration time
0,1
3000
s
1,0
103
P4.3
Deceleration time
0,1
3000
s
1,0
104
P4.4
DC braking
current
Unit
dep.
Unit
dep.
A
Varies
507
P4.5
0,00
600.00
s
0
516
0
= DC brake is off at
start
P4.6
Frequency to start
DC braking during
ramp stop
0,10
10,00
Hz
1,50
515
P4.7
0,00
600.00
s
0
508
0
= DC brake is off at
stop
P4.8
0
3
520
0
= Off
2
= Chopper
1
= On
3
= Full mode
P4.9
Flux braking current
0
7,4
A
519
P4.10 Ramp shape 2
0,0
10,0
s
0,0
501
0
= Linear
>0
= S-curve ramp time
P4.11 Acceleration time 2
0,1
3000
s
1,0
502
P4.12 Deceleration time 2
0,1
3000
s
1,0
503
Table 8.5: Motor control parameters
Code
Parameter
Min
Max
Unit
Default
ID
Note
P5.1
0
6
1
403
0
= Not used
1
= DI1
2
= DI2
3
= DI3
4
= DI4
5
= DI5
6
= DI6
P5.2
0
6
2
404 As parameter 5.1
P5.3
0
6
0
412 As parameter 5.1
P5.4
0
6
0
405 As parameter 5.1
P5.5
0
6
0
406 As parameter 5.1
P5.6
0
6
5
414 As parameter 5.1
P5.7
0
6
0
407 As parameter 5.1
Table 8.6: Digital inputs