Parameters 43
8
8.11 PI CONTROL PARAMETERS (CONTROL PANEL: MENU PAR -> P12)
NOTE!
These parameters are shown, when
P13.1 = 0.
Code
Parameter
Min
Max
Unit Default
ID
Note
P12.1 PI activation
0
2
0
163
0
= Not used
1
= PI for motor control
2
= PI for external use
P12.2 PI controller gain
0,0
1000
%
100,0
118
P12.3
0,00
320,0
s
10,00
119
P12.4
Keypad PI
reference
0,0
100,0
%
0,0
167
P12.5 Setpoint source
0
3
0
332
0
= Keypad PI reference,
P12.4
1
= Fieldbus
2
= AI1
3
= AI2
P12.6 Feedback source
0
2
2
334
0
= Fieldbus
1
= AI1
2
= AI2
P12.7
0,0
100,0
%
0,0
336 0 = No minimum scaling
P12.8
0,0
100,0
%
100,0
337
100,0 = No maximum
scaling
P12.9
Error value
inversion
0
1
0
340
0
= No inversion (Feed-
back<Setpoint->Increase
PI Output)
1
= Inverted
(Feedback<Setpoint-
>Decrease PI Output)
Table 8.11: PI control parameters