ENGINEERING MANUAL OF AUTOMATIC CONTROL
INDIVIDUAL ROOM CONTROL APPLICATIONS
416
Fig. 28. Cycle II with Enhanced Digital Control.
On mor ning occupanc y star tup, the fan oper ates with the hot
water v alve open, the f ace damper open, and the O A damper
closed; and as the r oom war ms to a v ent/r ecircula te setpoint,
the O A damper opens to a minim um v entila tion position. As
the hea ting load dr ops, the f ace and b ypass damper s modula te
to maintain the r oom hea ting temper atur e setpoint. As the r oom
temper atur e rises to a value midpoint betw een the hea ting and
cooling setpoints, the hea ting v alve closes. If the r oom
temper atur e r ises to the cooling setpoint, the O A damper
modulates to maintain the cooling setpoint.
Although the disc har ge air sensor could be used as a lo w
limit onl y, Figur e 28 shows it as the pr imar y contr oller r eset
from the demands of the r oom sensor .
In the unoccupied mode , the v alve is contr olled in a tw o-
position manner to maintain an unoccupied con
vection hea ting
room temperature setpoint. If the room temperature cannot be
maintained b y convection hea ting, the fan is cycled to maintain
the unoccupied hea ting f an-on setpoint. The face damper is
open and the O A damper is c losed.
Figur e 29 ad ds a c hilled w ater coil to F igur e 28.
RA
FAN
M15315
OA
CONTROL
PROGRAM
24
22.5
8
77
WALL MODULE
22.5
TEMPERATURE
HEATING
SETPOINT
COOLING
SETPOINT
00
24
00
PERCENT OPEN
TO OUTSIDE AIR
PERCENT OPEN
TO BYPASS
OPEN
CLOSED
MINIMUM
RECIRCULATE
SETPOINT
HEATING
SETPOINT
COOLING
SETPOINT
HEATING LOAD
PERCENT
COOLING LOAD
PERCENT
100
100
0
0
HOT WATER VALVE
HOT WATER VALVE
OUTSIDE AIR
DAMPER
FACE
DAMPER
FAN ON
OCCUPIED MODE
OPEN/ON
CLOSED/OFF
FAN ON
SETPOINT
CONVECTION
SETPOINT
FACE DAMPER
FAN
UNOCCUPIED MODE
OA DAMPER
CLOSED
13
41
0
100
0
100
DISCHARGE
TEMPERATURE
SETPOINT
HEATING
LOAD
PERCENT
COOLING
LOAD
PERCENT
DISCHARGE
TEMPERATURE
SETPOINT
24
13
MINIMUM
VENTILATION
DAMPER
SETPOINT
13
ON
PERCENT
OPEN
Summary of Contents for AUTOMATIC CONTROL SI Edition
Page 1: ...AUTOMATIC CONTROL for ENGINEERING MANUAL of COMMERCIAL BUILDINGS SI Edition ...
Page 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Page 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Page 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Page 66: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL PSYCHROMETRIC CHART FUNDAMENTALS 56 ...
Page 128: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Page 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 208: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 198 ...
Page 493: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 483 INDEX ...
Page 506: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 496 NOTES ...
Page 507: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 497 NOTES ...
Page 508: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 498 NOTES ...
Page 509: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 499 NOTES ...
Page 510: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 500 NOTES ...
Page 511: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 501 NOTES ...
Page 512: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 502 NOTES ...