CHILLER, BOILER, AND DISTRIBUTION SYSTEM CONTROL APPLICATIONS
365
System Objectives
The chilled water control and distribution system should:
1. Provide the minimum flow of chilled water through the
chiller as specified by the manufacturer.
2. Provide a stable pressure difference across supply and
return mains.
3. Prevent freeze-up in chiller and/or coils exposed to
outdoor air.
4. Control system pumps and bypass valves to prevent short-
cycling of pumps or radical pressure changes across
control valves at the terminal units.
In addition, for systems with two or more chillers operating
at once, the chilled water control and distribution system should:
1. Prevent return water from mixing with chilled water
before leaving the chiller plant.
2. Shut off flow through idle chiller(s).
Control of Terminal Units
The heat transfer characteristic is close to linear for a cooling
coil (Fig. 98) because the air to water temperature difference is
lower than that for hot water coils. This means a valve with
either a linear characteristic or an equal percentage characteristic
plug is satisfactory.
Fig. 98. Typical Heat Transfer Characteristic of
a Cooling Coil Supplied with Chilled Water.
DUAL TEMPERATURE SYSTEMS
Figure 99 shows a typical arrangement where the same pipes
carry hot water for heating or chilled water for cooling to the
same terminal units. These are usually fan coil units.
FLOW IN GPM
T
O
T
A
L
HEA
T
REMO
VED
C2403
Fig. 99. Two-Pipe Dual-Temperature System.
The three-way valves on the chiller and boiler are used for
changeover. The valve on the chiller is controlled two-position.
The three-way boiler valve is controlled modulating for heating
so that the hot water supply temperature may be reset from the
outside temperature. Boiler minimum flow or temperature may
require system modifications.
Changeover from heating to cooling can be based on outdoor
air temperature, solar gain, outdoor wet-bulb temperature, or a
combination. System bypass or other pressure control method
may also be required for such systems.
Changeover Precautions
A time delay in changing the operation from hot to chilled water
or vice versa is required to avoid putting hot water into the chiller
or chilled water into the boiler. A deadband between heating and
cooling will usually provide enough delay. Hot water to the chiller
can cause the compressor to cut out from high pressure and/or
damage the compressor. Chilled water to the boiler can cause
thermal shock to the boiler and/or flue gases to condense on the
fireside. Protection for boilers is covered in DUAL BOILER
PLANT CONTROL. For chillers a maximum entering water of
27
°
C is required to avoid excessive refrigerant pressure. A
thermostatic interlock can provide this safety feature.
MULTIPLE-ZONE DUAL-TEMPERATURE SYSTEMS
Since different zones often have different changeover
requirements, it is often necessary to furnish hot water to one
zone and chilled water to another, as in a curtain wall building
with high solar loads.
Figure 100 uses three-way valves V1 through V4 operating
two position to accomplish zone changeover. In large systems,
two-way valves may offer a tighter isolation of the hot and
chilled water circuits than three-way valves.
BOILER
CHILLER
AIR
SEPARATOR
TERMINAL
UNITS
2-POSITION
3-WAY VALVE
MODULATING
3-WAY VALVE
PUMP
C2920
Summary of Contents for AUTOMATIC CONTROL SI Edition
Page 1: ...AUTOMATIC CONTROL for ENGINEERING MANUAL of COMMERCIAL BUILDINGS SI Edition ...
Page 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Page 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Page 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Page 66: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL PSYCHROMETRIC CHART FUNDAMENTALS 56 ...
Page 128: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Page 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 208: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 198 ...
Page 493: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 483 INDEX ...
Page 506: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 496 NOTES ...
Page 507: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 497 NOTES ...
Page 508: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 498 NOTES ...
Page 509: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 499 NOTES ...
Page 510: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 500 NOTES ...
Page 511: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 501 NOTES ...
Page 512: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 502 NOTES ...