ENGINEERING MANUAL OF AUTOMATIC CONTROL
DAMPER SELECTION AND SIZING
459
Fig. 30. Damper System Characteristics of
Opposed Blade Dampers.
To achieve performance closest to the ideal linear flow
characteristic, a characteristic ratio of 2.5 for parallel blade
dampers (Fig. 29) and 10 for opposed blade dampers (Fig. 30)
should be used. The percent of the total resistance needed by
the damper can be determined by:
Total resistance (100%) = damper resi series
resistance
Substituting (total resistance – damper resistance)
for series resistance:
Characteristic ratio
(Fig. 29 and 30) =
series resistance
damper resistance
Fig. 29. Damper System Characteristics of
Parallel Blade Dampers.
100
0
0
% DAMPER OPENING
% FULL AIRFLOW
C1498
100
CHARACTERISTIC RATIOS =
SERIES RESISTANCE
DAMPER RESISTANCE
INHERENT
CHARACTERISTIC
20 10 5 3
2
1
100
0
0
% DAMPER OPENING
% FULL AIRFLOW
C1499
100
CHARACTERISTIC RATIOS =
SERIES RESISTANCE
DAMPER RESISTANCE
INHERENT
CHARACTERISTIC
5
3
1
20 10
or
For parallel blade dampers:
Damper resistance = 29% of total resistance
or
For opposed blade dampers:
or damper resistance = 9% of total resistance
For example, if a coil (Fig. 31) with a pressure drop of 0.140 kPa
is located in series with an opposed blade damper, the damper
should have a pressure drop of 0.014 kPa (10 percent of 0.140
= 0.014).
2.5 =
100
damper resistance
– 1
10 =
100
damper resistance
– 1
9
100 – 9
= 10% of series resistance
Characteristic ratio =
total resistance – damper resistance
damper resistance
=
total resistance
damper resistance
– 1
29
100 – 29
= 41% of series resistance
Fig. 31. Typical Pressure Drop for Coil and
Damper (Series Resistance).
DETERMINING DAMPER SIZE
The desired relationship of damper resistance to series
resistance developed in DAMPER CHARACTERISTICS is
used to determine the desired damper pressure drop. This
pressure drop is then used in the damper sizing procedure in
Table 4.
For example, for a 915 mm by 1625 mm (1.487 m
2
) duct
with an airflow of 9.45 m
3
/s and a pressure drop of 0.014 kPa
across a parallel blade damper, determined the damper size as
shown in Table 5.
(Fig. 29 and 30)
0.014 kPa
DROP
0.140 kPa
DROP
M15303
Summary of Contents for AUTOMATIC CONTROL SI Edition
Page 1: ...AUTOMATIC CONTROL for ENGINEERING MANUAL of COMMERCIAL BUILDINGS SI Edition ...
Page 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Page 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Page 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Page 66: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL PSYCHROMETRIC CHART FUNDAMENTALS 56 ...
Page 128: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Page 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 208: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 198 ...
Page 493: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 483 INDEX ...
Page 506: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 496 NOTES ...
Page 507: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 497 NOTES ...
Page 508: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 498 NOTES ...
Page 509: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 499 NOTES ...
Page 510: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 500 NOTES ...
Page 511: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 501 NOTES ...
Page 512: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 502 NOTES ...