ENGINEERING MANUAL OF AUTOMATIC CONTROL
CHILLER, BOILER, AND DISTRIBUTION SYSTEM CONTROL APPLICATIONS
390
Table 11. Description of Figure 138 Reference Points.
Control Strategies:
1. Primary temperatures: supply up to 130
°
C, return up to
90
°
C.
2. Secondary temperatures: supply up to 90
°
C, return up
to 70
°
C.
3. System provides a SSF temperature depending on the
outdoor temperature according to a reset schedule
(Fig. 139).
4. Heat demand dependent pump switching, with one full
cycle of the pump per day to prevent seizing.
5. Diagnostic functions via connector.
6. PRF temperature limitation with fixed and variable value
available. The control valve reduces the flow until the PRF
temperature is below the parameter value. The setpoint can
be fixed or floating with a certain
∆
T below the PSF.
7. SSF temperature limitation available (parameter).
Reference
Description
Reference
Description
DDC
Controller
TIC 24
SRF temperature
TI 01
Outdoor air temperature
TZA+ 21
Safety temperature limit (SSF)
TI 31
Room temperature sensor &
setpoint setting
Y 11
Control valve PRF
TIC 12
PRF temperature
Y 23
Circulating pump
TIC 22
SSF temperature
Fig. 139. SSF Temperature Reset Schedule.
Reference
Description
Reference
Description
DDC
Controller
TIC 16
PRF–temperature
PI 11
PSF pressure
TIC 21
DHW temperature (supply flow)
PI 17
PRF Pressure
TIC 31
SSF temperature
PI 22
DHW pressure (supply flow)
TIC 34
SRF temperature
PI 24
DHW pressure (return flow)
Y 13
Actuator valve (SSF temperature control)
PI 28
Cold water pressure
Y 14
Actuator valve (DHW temperature control)
PI 213
DHW network pressure
Y 23
Actuator valve (DHW supply flow)
PIC 32
SSF pressure
Y 25, 26, 27
DHW circulating pumps
PIC 35
SRF pressure
Y 29, 210
DHW pressure booster pumps
QIR 02
Elec. Power metering
Y 31
Actuator valve (SSF)
QIR 15
Heat metering
Y 36, 37
Circulating pumps (secondary fl.)
QIR 214
Drinking water metering
Y 38, 39
Refill pumps (PRF to SRF)
TI 01
Outdoor air temperature
Y 211, 212
DHW pressure booster pumps
TI 12
PSF temperature
Y 310
Actuator valve
TI 215
DHW circulation, return flow temperature
CONTROL OF APARTMENT BUILDING SUBSTATIONS WITH DOMESTIC HOT WATER
DDC Control of Two-Stage Heat Exchanger for Heating and Domestic Hot Water.
Table 12. Description of Figure 140 Controls.
90
80
70
10
18
OUTSIDE AIR TEMPERATURE (
°
C)
SSF TEMPERA
TURE
(
°
C)
M15295
0
-20
-10
100
110
120
130
Summary of Contents for AUTOMATIC CONTROL SI Edition
Page 1: ...AUTOMATIC CONTROL for ENGINEERING MANUAL of COMMERCIAL BUILDINGS SI Edition ...
Page 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Page 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Page 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Page 66: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL PSYCHROMETRIC CHART FUNDAMENTALS 56 ...
Page 128: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Page 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 208: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 198 ...
Page 493: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 483 INDEX ...
Page 506: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 496 NOTES ...
Page 507: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 497 NOTES ...
Page 508: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 498 NOTES ...
Page 509: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 499 NOTES ...
Page 510: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 500 NOTES ...
Page 511: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 501 NOTES ...
Page 512: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 502 NOTES ...