ENGINEERING MANUAL OF AUTOMATIC CONTROL
INDIVIDUAL ROOM CONTROL APPLICATIONS
404
Fig. 7. Induction VAV Air Terminal Unit.
The induction VAV ATU maintains mor e air motion in the
space a t lower loads than a thr ottling VAV ATU. The r ehea t
coil is optional, and ma y be in the induced air or suppl y air.
Parallel Fan ATU
The par allel fan ATU (F ig. 8) r eplaces the induction VAV
ATU damper s with a small centr ifugal fan to r ecirculate r etur n
air a t a constant v olume after pr imar y air decr eases. The fan
acts as the f irst sta ge of reheat after pr imar y flow is at minim um
or can be s witched on a t a lo w pr imar y flow thr eshold w hile
pr imar y flow goes to zero. The r ehea t coil is optional.
The oper ation c ycle in F igur e 8 shows tha t when space
temper atur e is below the hea ting setpoint, the pr imar y air f low
is at a minim um, and the f an is on. As the hea ting load g oes to
zero, the r eheat valve closes, then the f an stops. After the space
temperature rises through a deadband, as the cooling load
incr eases, the pr imar y air f low incr eases to maxim um.
Series Fan ATU
The ser ies fan ATU (F ig. 9) deliver s a constant v olume of
dischar ge air with a v ar iable volume of AHU suppl y air. In this
ATU, the fan is on contin uously dur ing occupied hour s. Pr imar y
air is modula ted to meet space demand f or cooling . As pr imar y
air damper modula tes closed, mor e plen um air is dr awn in to
maintain a constant disc har ge volume . Optional r ehea t can be
sequenced as required.
00
24
24
24
13
0.35
0.165
0.465
-1.5
0.575
58
MINIMUM
MAXIMUM
kPa
CURRENT
AIRFLOW
(m
3
/s)
PERCENT OPEN
AIRFLOW SETPOINTS (m
3
/s)
HEATING
DEADBAND
COOLING
SETPOINT
TEMPERATURE
WALL MODULE
PLENUM AIR
RHC
VAV BOX
MAX
PRIMARY
AIRFLOW
POSITION
REHEAT
MIN
ZERO
FULL
FULL
0
0
DEADBAND
(ADJUSTABLE)
M15308
HEATING
LOAD
HEATING SETPOINT
COOLING SETPOINT
COOLING
LOAD
PRIMARY
DAMPER AIRFLOW
INDUCTION
DAMPER
POSITION
OPEN
CLOSED
INDUCTION
DAMPER
PRIMARY
AIR
Summary of Contents for AUTOMATIC CONTROL SI Edition
Page 1: ...AUTOMATIC CONTROL for ENGINEERING MANUAL of COMMERCIAL BUILDINGS SI Edition ...
Page 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Page 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Page 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Page 66: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL PSYCHROMETRIC CHART FUNDAMENTALS 56 ...
Page 128: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Page 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 208: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 198 ...
Page 493: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 483 INDEX ...
Page 506: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 496 NOTES ...
Page 507: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 497 NOTES ...
Page 508: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 498 NOTES ...
Page 509: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 499 NOTES ...
Page 510: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 500 NOTES ...
Page 511: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 501 NOTES ...
Page 512: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 502 NOTES ...