BUILDING MANAGEMENT SYSTEM FUNDAMENTALS
ENGINEERING MANUAL OF AUTOMATIC CONTROL
195
CONTROL GRAPHICS
Many digital control strategies require fine tuning to assure
systems are staged and loaded without excessive surging and
cycling. Such strategies are often more comprehensive if
presented as a “Dynamic Sequence” where the specified
sequence is repeated with dynamic commandable values
embedded (Fig. 9).
DATA PENETRATION
Figures 7, 8, and 9 present data penetration concepts from
the macro to the micro levels. Graphics should be designed for
each specific operator type. For example, a security guard is
required to monitor certain critical alarm points after hours,
design special graphics of only those points, with simplified
explanations, and specific operator response messages. Use
simplified floor plan graphics with appropriately positioned
dynamic space temperatures for zone controllers. Selection of
the VAV icon (controller) presents the specified points (setpoint,
min-max airflow, damper position, etc.) on a terminal unit
graphic.
All system points should be positioned on graphics and certain
points should be specified on multiple graphics.
Fig. 9. Typical Graphic to Aid System Fine Tuning in the Field.
MINIMUM
CHILLED WATER SETPOINT
ANYTIME ANY AHU VALVE IS OPEN GREATER THAN %FOR MORE THAN
MINUTES AND THE TIME IS BEFORE , THE LEAD CHILLED WATER PUMP STARTS.
ANYTIME BOTH CHILLERS ARE RUNNING AND THE CHILLED WATER DIFFERENTIAL
TEMPERATURE IS LESS THAN KELVINS FOR MORE THAN MINUTES, THE
LAG CHILLER PUMP STOPS AND REMAINS OFF AT LEAST MINUTES.
MAXIMUM
CURRENT
7
20
3
1545
0.5
2.4
4.0
30
ANYTIME ONLY ONE CHILLER IS RUNNING AND ALL AHU CHILLED WATER VALVES ARE
LESS THAN % OPEN AND THE CHILLER PLANT DIFFERENTIAL TEMPERATURE
IS LESS THAN KELVINS, THE CHW TEMPERATURE SETPOINT INCREMENTS UP AT
THE RATE OF KELVINS EVERY MINUTES
ANYTIME ANY AHU CHILLED WATER VALVE IS FULL OPEN, THE CHW TEMPERATURE
SETPOINT DECREMENTS DOWN AT THE SAME RATE
5
90
90
3.0
0.2
4
ANYTIME THE LEAD CHILLER HAS RUN LONGER THAN MINUTES, THE CHILLED
WATER TEMPERATURE IS GREATER THAN DEGREES ABOVE SETPOINT FOR
MINUTES, THE BYPASS VALVE IS CLOSED, AND THE TIME IS BEFORE ,
THE LAG CHILLER STARTS.
1545
8
11
CHILLED WATER SYSTEM
M15135
Summary of Contents for AUTOMATIC CONTROL SI Edition
Page 1: ...AUTOMATIC CONTROL for ENGINEERING MANUAL of COMMERCIAL BUILDINGS SI Edition ...
Page 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Page 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Page 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Page 66: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL PSYCHROMETRIC CHART FUNDAMENTALS 56 ...
Page 128: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Page 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 208: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 198 ...
Page 493: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 483 INDEX ...
Page 506: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 496 NOTES ...
Page 507: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 497 NOTES ...
Page 508: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 498 NOTES ...
Page 509: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 499 NOTES ...
Page 510: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 500 NOTES ...
Page 511: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 501 NOTES ...
Page 512: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 502 NOTES ...