ENGINEERING MANUAL OF AUTOMATIC CONTROL
PNEUMATIC CONTROL FUNDAMENTALS
92
SUPPLY FAN CONTROL SEQUENCE
Any time the Supply Fan (Fig. 76) runs, the pressure
controller with the greatest demand, Static Pressure Controller
PC
1
or PC
2
, operates the Electronic-Pressure Transducer PT.
The controller used is determined by High Pressure Selector
Relay HSR. Transducer PT controls the Supply Fan Variable
Speed Drive (VSD) to maintain duct static pressure. The pick-
up probes for Static Pressure Controllers PC
1
and PC
2
are located
at the end of the east and west zone ducts.
Fig. 76. Supply Fan Load Control.
RETURN FAN CONTROL SEQUENCE
Static Pressure Controller PC (Fig. 77) controls the return
fan variable speed drive to maintain space static pressure. The
pick-up probe is located in the space
NOTE: 1. Because of varying exhaust between occupied and
warm-up modes, space static pressure control of
the return fan is selected. Return fan tracking from
supply fan airflow is acceptable but is complex if
varying exhaust is worked into the control scheme.
2. Exercise care in selecting location of the inside
pickup and in selection of the pressure controller.
Location of the reference pickup above the roof is
recommended by ASHRAE.
3. To prevent unnecessary hunting by the return fan
at start-up, the supply fan control signal should be
slow loading such that the supply fan goes from
zero or a minimum to maximum load over three
minutes. Shut down should not be restricted.
WARM-UP/HEATING COIL CONTROL
SEQUENCE
Any time the Supply Fan (Fig. 78) runs and the return air
temperature is below 20.5
°
C, Temperature Controller TC-1 trips
Snap-Acting Relay SA-1 to position Switching Relays SR-1
and SR-2 to initialize warm-up control. Relay SA-1 also
positions Switching Relay SR-4 to disable cooling controls.
Switching Relay SR-2 opens all interior VAV box dampers and
starts the hot water pump. Relay SR-1 switches the hot water
valve from normal control to warm-up control via Controller
TC-2 and modulates the hot water valve to maintain a discharge
air temperature setpoint of 32
°
C.
NOTE: Fan powered perimeter VAV boxes are cool in this
mode and operate with the fans on and at the minimum
airflow (warm air) setpoints. Reheat valves at each
box operate as needed. This allows the warm-up cycle
to operate the air handling unit (AHU) fans at a
reduced and low cost power range.
Fig. 77. Return Fan Load Control.
VSD
L
B
RA
350 Pa
RA
350 Pa
PC
2
PC
1
M
2
EP
H
B
P
2
P
1
L
B
M
H
PT
SUPPLY FAN
M15143
STARTER
EAST ZONE
WEST ZONE
HSR
VSD
REFERENCE PICK-UP
RUN TO 5 METERS
ABOVE ROOF
L
B
DA
12 Pa
PC
M
2
EP
H
1
PT
TO SPACE
STATIC PRESSURE
PICK-UP
RETURN FAN
M15144
STARTER
Summary of Contents for AUTOMATIC CONTROL SI Edition
Page 1: ...AUTOMATIC CONTROL for ENGINEERING MANUAL of COMMERCIAL BUILDINGS SI Edition ...
Page 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Page 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Page 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Page 66: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL PSYCHROMETRIC CHART FUNDAMENTALS 56 ...
Page 128: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Page 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 208: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 198 ...
Page 493: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 483 INDEX ...
Page 506: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 496 NOTES ...
Page 507: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 497 NOTES ...
Page 508: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 498 NOTES ...
Page 509: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 499 NOTES ...
Page 510: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 500 NOTES ...
Page 511: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 501 NOTES ...
Page 512: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 502 NOTES ...