PSYCHROMETRIC CHART FUNDAMENTALS
ENGINEERING MANUAL OF AUTOMATIC CONTROL
51
COOLING AND DEHUMIDIFICATION
BASIC PROCESS
Cooling and dehumidification can be accomplished in a single
process. The process line moves in a decreasing direction across
both the dry-bulb temperature lines and the constant moisture
lines. This involves both sensible and latent cooling.
Figure 12 illustrates cooling air by removing sensible heat
only. In that illustration, the resulting cooled air was 95 percent
relative humidity, a condition which often calls for reheat (see
DEHUMIDIFICATION AND REHEAT). Figure 25 illustrates
a combination of sensible and latent cooling. Whenever the
surface temperature of the cooling device (Point B), such as a
chilled water coil, is colder than the dew point temperature of
the entering air (Point A), moisture is removed from the air
contacting the cold surface. If the coil is 100 percent efficient,
all entering air contacts the coil and leaving air is the same
temperature as the surface of the coil.
Fig. 25.
All coils, however, are not 100 percent efficient and all air
does not come in contact with the coil surface or fins. As a
result, the temperature of the air leaving the coil (Point C) is
somewhere between the coolest fin temperature (Point B) and
the entering outdoor air temperature (Point A). To determine
this exact point requires measuring the dry-bulb and wet-bulb
temperatures of the leaving air.
To remove moisture, some air must be cooled below its
dew point. By determining the wet-bulb and the dry-bulb
temperatures of the leaving air, the total moisture removed per
kilogram of dry air can be read on the humidity ratio scale and
is determined as follows:
1. The entering air condition is 30
°
C dry bulb and 61 percent
rh (Point A). The moisture content is 16.5 grams of
moisture per kilogram of dry air.
2. The leaving air condition is 15
°
C dry bulb and 93 percent
rh (Point C). The moisture content is 10 grams of moisture
per kilogram of dry air.
3. The moisture removed is:
16.5 g/kg – 10 g/kg = 6.5 grams of moisture
per kilogram of dry air
The volume of air per kilogram at 30
°
C dry bulb and 24
°
C
wet bulb (Point A) is 0.881 cubic meters per kilogram of dry
air. If 2.5 cubic meters of air per second passes through the
coil, the weight of the air is as follows:
2.5 m
3
/s
÷
0.881 m3/kg
=
2.84 kilograms per
second
The kilograms of water removed is as follows:
2.84 kg/s x 16.5 g/kg
= 46.9 grams per second
or
AIR WASHERS
Air washers are devices that spray water into the air within a
duct. They are used for cooling and dehumidification or for
humidification only as discussed in the HUMIDIFYING
PROCESS—AIR WASHERS section. Figure 26 illustrates an
air washer system used for cooling and dehumidification. The
chiller maintains the washer water to be sprayed at a constant
10
°
C. This allows the chilled water from the washer to condense
water vapor from the warmer entering air as it falls into the
pan. As a result, more water returns from the washer than has
been delivered because the temperature of the chilled water is
lower than the dew point (saturation temperature) of the air.
The efficiency of the washer is determined by the number and
effectiveness of the spray nozzles used and the speed at which
the air flows through the system. The longer the air is in contact
with the water spray, the more moisture the spray condenses
from the air.
46.9 g/s x 60 x 60
1000g/kg
= 176.0 kilograms per hour
A
B
C
10
°
C DB 15
°
C DB
93% RH
30
°
C DB
61% RH
0.881 m /kg
14.5
°
C WB
16.5 g/kg
10 g/kg
24
°
C WB
30
°
C DB
61% RH
OA
10
°
C DB
SUPPLY FAN
15
°
C DB
93% RH
DA
C4334
COOLING COIL
3
Summary of Contents for AUTOMATIC CONTROL SI Edition
Page 1: ...AUTOMATIC CONTROL for ENGINEERING MANUAL of COMMERCIAL BUILDINGS SI Edition ...
Page 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Page 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Page 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Page 66: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL PSYCHROMETRIC CHART FUNDAMENTALS 56 ...
Page 128: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Page 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 208: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 198 ...
Page 493: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 483 INDEX ...
Page 506: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 496 NOTES ...
Page 507: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 497 NOTES ...
Page 508: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 498 NOTES ...
Page 509: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 499 NOTES ...
Page 510: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 500 NOTES ...
Page 511: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 501 NOTES ...
Page 512: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 502 NOTES ...