ENGINEERING MANUAL OF AUTOMATIC CONTROL
INDIVIDUAL ROOM CONTROL APPLICATIONS
402
Fig. 5. Variable Air Volume Single-Duct Air Terminal Unit.
Figure 5 displays the primary supply air temperature and static
pr essur e. These values ar e da ta points in the AHU dig ital
contr oller and not ph ysical points a t the VAV box. They will
var y when measur ed at the VAV boxes. When a BMS user looks
at a VAV box displa y, it is usuall y because a pr oblem exists.
The fan system suppl y air temper atur e and sta tic pr essur e ar e
necessary data for problem analysis.
Variable Air Volume ATU with Electr
ic Rehea
t
The VAV ATU with electr ic reheat in F igur e 6 ad ds r eheat to
Figur e 5. Figur e 6 also sho ws four bo xes on one displa y. The
cooling PID varies the box airflow from maximum to minimum
as the cooling load drops to maintain setpoint. If the cooling
load dr ops fur ther , the space temper atur e dr ops thr ough a dead
band until the heating setpoint is reached, at which point the
heating unit is contr olled to maintain the hea ting setpoint. When
electric reheat is used, the heating PI may be modified with
softwar e hea t anticipa tion to ad vance the hea ter sta ges off
command to minimize wide swings in space temperature which
would result from simple temperature sensed control.
Although F igur es 3, 4, 5, and 6 sho w sever al inputs, outputs,
and setpoints, man y mor e par ameter s ar e availa ble and
necessar y to allow technicians to ada pt the standar d pr ogr am
to a unique r oom and set of equipment. These ad ditional
parameters, usually addressable and commandable from the
BMS or portable terminal, include the cooling loop PI gains,
the heating loop PI gains, reheat airflow setpoint, unoccupied
space temperature setpoint, standby temperature setpoint,
temper atur e sensor calibr ation offset, bypass push-b utton sta tus,
bypass push-b utton o verride time in min utes, smoke pur ge mode
% of maximum airflow setpoint, smoke pressurization mode
% of maximum airflow setpoint, and unoccupied mode % of
maximum airflow setpoint.
NOTE: On-off electr ic heat contr ol often r equir es a minim um
air velocity above that of the minimum cooling airflow
to pr event e xcessive heating element temper atur es.
Constant
Air Volume ATUs
The constant air v olume (CAV) ATUs ar e similar to the
pr essur e independent VAV units, except the y contr ol at a single
air v olume setpoint. They usuall y include r ehea t coils, an
associated room sensor that controls the heating, and are often
found connected to VAV AHUs which also ha ve VAV boxes
and the associa ted var ying duct sta tic pr essur es. CAV units ar e
used wher e the r oom suppl y air v olume m ust be maintained a t
a constant v alue.
Induction
VAV ATU
The induction VAV ATU (Fig. 7), uses induced r etur n air as
the initial r ehea t medium. Induction VAV ATUs ar e usuall y
installed a bove the ceiling and dr aw retur n air fr om the plen um
created b y a false ceiling. The contr oller r esets the pr imar y air
airflow control setpoint in unison to opening the return air
damper s per the oper ation c ycle shown in F igur e 7. As the
dampers open, more return air is induced into the unit and
recirculated into the space.
M15306
24
13
0.35
52
0.165
1.445
0.543
24
MINIMUM
AIRFLOW
SETPOINT
(m
3
/s)
kPa
MAXIMUM
AIRFLOW
SETPOINT
(m
3
/s)
CURRENT
AIRFLOW
(m
3
/s)
CURRENT SPACE
TEMPERATURE
SETPOINT
CURRENT SPACE
TEMPERATURE
AIRFLOW
ZERO
ADJUSTABLE
MINIMUM
AIRFLOW
ADJUSTABLE
MAXIMUM
AIRFLOW
LOW
HIGH
SPACE COOLING LOAD
PERCENT
OPEN
PRIMARY
AIR
Summary of Contents for AUTOMATIC CONTROL SI Edition
Page 1: ...AUTOMATIC CONTROL for ENGINEERING MANUAL of COMMERCIAL BUILDINGS SI Edition ...
Page 4: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL iv ...
Page 6: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL vi ...
Page 46: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL CONTROL FUNDAMENTALS 36 ...
Page 66: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL PSYCHROMETRIC CHART FUNDAMENTALS 56 ...
Page 128: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL ELECTRIC CONTROL FUNDAMENTALS 118 ...
Page 158: ...MICROPROCESSOR BASED DDC FUNDAMENTALS 148 ENGINEERING MANUAL OF AUTOMATIC CONTROL ...
Page 208: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL BUILDING MANAGEMENT SYSTEM FUNDAMENTALS 198 ...
Page 493: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 483 INDEX ...
Page 506: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 496 NOTES ...
Page 507: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 497 NOTES ...
Page 508: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 498 NOTES ...
Page 509: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 499 NOTES ...
Page 510: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 500 NOTES ...
Page 511: ...INDEX ENGINEERING MANUAL OF AUTOMATIC CONTROL 501 NOTES ...
Page 512: ...ENGINEERING MANUAL OF AUTOMATIC CONTROL INDEX 502 NOTES ...