94
address Function Code
Register
address
Register
number
Register
content
bytes
Register
content
Checksum
Request
0x01
0x10
0x3200 0x0002
0x04
0x01C7,
0x1388
0x0399
Response
0x01
0x10
0x3200 0x0002
none
none
0x4F70
Read 1 # Inverter output current, the Inverter responds output current of 30.0 A
(internally donote to be 300)
:
address Function Code
Register
address
Register number or
read number of bytes
Register
content
Checksum
Request
0x01
0x03
0x3306
0x0001
none
0x6B4F
Response
0x01
0x03
none
0x02
0x012C
0xB809
10.4
The scaling rule of Inverter
A
)
The calibration of frequency is 1:100
To make inverter running at 50 hz, the main setting should be 0 x1388
(
5000
)
.
B
)
The calibration of time is 1:10
To make the acceleration time to be 30s, the function code setting
should be 0x012c
(
300
)
.
C
)
The calibration of current is1:10
If the feedback current of inverter is 0x012c
,
the current of the inverter is 30A.
D
)
Output power is its absolute value.
E
)
Other issues(such as input and output terminals, etc.), please refer to the user
manual.