As Figure 6-70 shows, the inverter holds the frequency and direction of the
last stage after single cycle.
3
:
(
Continuous cycle
):
The inverter continues running cycle after cycle until
Stop command is received.
Ten’s place of FD.00: Restart mode after PLC interruption:
0: start from the first stage
The inverter restarts from the first stage of PLC after interrupts, such as Stop
command, fault or poweroff.
1: continue from the stage frequency where the inverter stops. When the
inverter stops caused by Stop command or fault, it can record the time that it
has undergone in the current stage. After receiving Run command, it will run
at the preset frequency of the stage for the remaining time of the stage
2
:
Start from the frequency where it stops:
When the inverter stops caused by Stop command or fault, it can record both
the time it has undergone in the current stage and the very frequency when the
inverter stops. It will pick up the recorded frequency and run for the remaining
time of the stage.
Hundred’s place of FD.00: Save PLC state after poweroff:
0: not save
The PLC state will not be saved when poweroff, and the inverter will start
from the first stage after powerup.
1: save
The PLC state, including the stage, frequency, run time will be saved when
poweroff and the inverter will start according to the setting of ten’s place of
FD.00 after powerup.
Thousand’s place: Selection of time unit:
0: Second
1: Minute
This unit is only valid for defining the PLC operating time. The unit of
Acc/Dec time in PLC operation is determined by F9.23.
FD.01 Stage 1 setting
Range
:
000
~
323
【
000
】
FD.02 Stage 1 run time
Range
:
0
~
6500s
(
min
)【
20.0s
】
FD.03 Stage 2 setting
Range
:
000
~
323
【
000
】
FD.04 Stage 2 run time
Range
:
0
~
6500s
(
min
)【
20.0s
】
FD.05 Stage 3 setting
Range
:
000
~
323
【
000
】
FD.06 Stage 3 run time
Range
:
0
~
6500s
(
min
)【
20.0s
】
FD.07 Stage 4 setting
Range
:
000
~
323
【
000
】