40
The signal is given if the preset frequency is higher than lower limit of
frequency and the operating frequency reaches the lower limit of frequency.
9: Zero-speed running
The signal is given if the inverter’s output frequency is 0 and the inverter is in
operating status.
10: Completion of simple PLC operation stages
The signal is given (pulse, 500ms) if the present stage of PLC operation is
finished.
11: PLC cycle completion indication
The signal (pulse, 500ms width) is given if one cycle of PLC operation is
finished.
12: preset counting value arrival
13: reference length arrival
Refer to F6.11~F6.12.
14: Inverter running state
When inverter is in a state of reverse, output is actived
15: Inverter is ready (RDY)
The RDY signal is output when the inverter has no fault, its DC bus voltage is
normal; the Start Prohibit function is disabled. It is ready to start.
16: Inverter fails
The signal is given if the inverter has faults.
17: Extended function 1 of host
The output signal of terminal Y1 or TC is directly controlled by a serial port.
Refer to the communication protocol of HV950.
19: preset operating time out
The signal is given if the inverter’s total operating time (FN.01) reaches preset
operating time (FN.00).
F6.04 AO output function
Range
:
0
~
12
【
0
】
F6.05~F6.06 Reserved
Reserved
AO is analog output terminals.
Refer to section 3.3.2 for the output characteristics of AO
Refer to Table 6-9 for the function of F6.04
Table 6-9 Signals from AO
Setting
Function
Range
0
Output freq. before
compensation
0
~
Max. output freq.
1
Output freq. after
compensation
0
~
Max. output freq.
2
Preset freq.
0
~
Max. output freq.
3
Output current
0
~
2 times of inverter’s rated