24
6.
Parameters
Note
:
The contents in the“
【】
”are factory default.
6.1 Basic Parameters
(
F0
)
F0.00 Command channel
Range
:
0
~
2
【
0
】
HV950 has 3 kinds of command channels:
0
:
LED keypad display unit
,
use RUN and STOP key on the keypad to control
the inverter
.
1
:
Terminal control: Input operating commands via terminals. Use terminals
FWD, REV, to start and stop the inverter
2
:
Serial communication port control.
F0.01 Reserved
Reserved
Reserved
F0.02 Frequency source setting Range
:
0
~
6
【
0
】
0
:
Digital setting 1,set by ▲or▼key.
Initial frequency is the value of F0.04 and it can be adjusted via ▲ and ▼keys
on the keypad.
1
:
Digital setting 2 set by terminal UP/DN.
Initial frequency is the value of F0.02 and it can be adjusted via terminal
UP/DN.
2
:
Digital setting 3, set through serial communication port
Initial frequency is the value of F0.04 and it can be adjusted via serial
communication port.
3
:
Reserved
4
:
The reference frequency is set by AI input (0
~
10V/0
~
20mA ), the
frequency calculation curve is given in F5.10~F5.21
5
:
Reserved
6
:
Keypad Potentiometer Setting
F0.03 Auxiliaryreference frequency
Range
:
00
~
13
【
0
】
Method
Name
Description
0
Invalid
Auxiliary freq.=0
1
Adjust by ▲ and ▼
Default is F0.05
2
Adjust by UP/DN
3
Set by serial port
4
Reserved
Depending on actual input.