![HNC Electric HV950-1R5G1(B) User Manual Download Page 14](http://html.mh-extra.com/html/hnc-electric/hv950-1r5g1-b/hv950-1r5g1-b_user-manual_2142007014.webp)
14
Terminal strip layout
The layout is shown below
:
Y1
X1
X4
P24
PLC
+10V
X5
GND
X2
X3
COM
485+ 485-
AO
AI
TC
TB
TA
TA-TB
:
Normally closed
;
TA-TC
:
Normally open
Table 4-5 Terminal function table
Category
Terminals
Name
Function
Specification
Communication
485
+
RS485com
munication
port
RS485
+
(differential signal)
Standard RS-485
communication
port,
Please use
twisted-pair cable
or shielded cable
485-
RS485-(differential signal)
Analog input
AI
Analog
input
Accepting analog voltage/current
input.CN4 can select voltage or
current input mode
,
Voltage
input mode is the default
(
Reference ground
:
GND
)
Input voltage
range:0~10V
(input
resistance:100kΩ)
Input current
range:0~20mA
(input
resistance:500Ω)
resolution:1/2000
Analog output
AO
Analog
output
Be able to output analog
voltage/current, Jumper CN6 can
select voltage or current input
mode. Voltage input mode is the
default mode. Refer to F6.04 for
details (reference ground: GND)
Output current
range: 0/4~20mA
Output voltage
range: 0/2~10V
Digital input
X1
~
X5
Multi-funct
ional
digital
inputs 1
~
5
Can be defined as
multi-functional digital inputs,
see Section 7.6
Reference ground: COM
Optical-isolator
2-way input
input resistance:
2kΩ
maximum input
frequency: 200Hz
Input voltage
range: 9~30V
PLC
Common
terminal
Common terminal for
multi-functional inputs
P24
+24V
supply
Pro24V power supply
Output
:
+24V,set
point accuracy
:
±10%
Max output
current
:
200mA
COM
+24V
common
terminal
Isolated internally with GND
Isolated internally
with GND