6.2 Motor Parameter
(
F1
)
F1.00 Reserved
Reserved
F1.01 Motor’s poles Range
:
2
~
14
【
4
】
F1.02 Rated power
Range
:
0.4
~
1000kW
【
depending on model
】
F1.03 Rated current Range
:
0.1
~
999.9A
【
depending on model
】
F1.01~F1.03 is to set motor’s parameters. Be sure to input the values
according to motor’s nameplate.
F1.04 Current without
load
Range
:
0.1
~
6553A
【
depending on model
】
F1.05 Stator resistance
Range
:
0.0
~
50.00
%【
depending on
model
】
F1.06 Leakage
inductance
Range
:
0.0
~
50.00
%【
depending on
model
】
F1.07 Rotor resistance
Range
:
0.0
~
50.00
%【
depending on
model
】
F1.08 Mutual inductance
Range
:
0.0
~
2000.0
%【
depending on
model
】
After the success of the motor parameter self learning, P1.04 ~ P1.08
parameters will be automatically updated.
After change P1.02 motor rated power, P1.04 ~ P1.08 parameter value will be
back to the factory.
F1.09 Rated slip frequency Range
:
0.00
~
20.00Hz
【
0Hz
】
The motor rated speed can be obtained by the motor nameplate.
F1.10 Auto tuning
Range
:
0
~
2
【
0
】
0: Auto-tuning is disabled
1: Stationary auto-tuning (Start auto-tuning to a standstill motor
Before starting auto-tuning, values on the motor’s nameplate must be input
correctly (F1.01~F1.03). When starting auto-tuning to a standstill motor, the
stator’s resistance, rotor’s resistance and the leakage inductance will be
measured and the measured values will be written into F1.05, F1.06 and F1.07
automatically.
2
:
Rotating auto-tuning
When starting a rotating auto-tuning, at first, the motor is in standstill status,
and the stator’s resistance , rotor’s resistance and the leakage inductance will
be measured, and then the motor begins to rotate, mutual inductance,
parameters will be measured and written into F1.05, F1.06, F1.07, F1.08 and
F1.04 automatically.
After auto-tuning, F1.10 will be set to 0 automatically.