Table 7-2 Operation Related Faults and Solutions
Phenomena
Conditions
Possible reasons of fault
Actions
No
response of
keys
Part of the keys or
all the keys are
disabled
Keypad locked
In stop or operating state, keep
pressing FUNC/DATA key, when
pressing ▼ key three times.
Power off the inverter and then
power on again
Panel’s cables are not
well connected
Check the wiring
Panel’s keys are
damaged
Replay operation panel or seek
service
LED no
display
No LED
segmentilluminat
es
Not power on.
Power on
Keypad cable reverse
connected
Immediately remove the keypad
and connect it again correctly. If
the problem persists, please
connect our technical support
person.
Parameter
setting
cannot be
changed
Cannot be
changed during
operating
Parameter modification
property is ×
”
Settings of parameters can be
changed in stop status
Settings of part of
parameters cannot
be changed.
Set FP.01 to 1 or 2
Set FP.01 to 0
Parameter’s
modification property is
*
The parameters cannot be changed
by user
No parameter
but“0.0.0.0.” is
displayed when
pressing
PRG
User’s password is
required
Input correct user’s password
Seek service
Unexpecte
d stops
during
running
The inverter stops
automatically
without STOP
command. The
RUN indicator
goes out.
Alarm occurs
Find out the reason and reset.
Single cycle of PLC
finishes
Check PLC configuration
Interruption of the
communication between
the inverter and host or
flush mount faceplate
Check communication cables and
FB.02, FB.03 settings
Power failure
Check the power supply
Command input method
changed
Check the command input method
and corresponding parameter
Positive/negative logic
of control terminal
changed
Check F9.15.
The inverter stops
automatically
without STOP
command. The
RUN indicator is
still on,
zero-frequency
Auto reset of fault
Check reason of fault and the auto
reset function
Simple PLC pause
Check PLC pause function
(terminal)
Interrupt signal feedback
from external devices
Check the configuration of
external interrupt and faulty
external devices