76
F6 Group
:
Output Terminal Control Parameter
(
total 18
)
Code
Name
Setting Scope
Min Unit
Defaulted
Value
Address
Change
F6.15
FDT1 lag
0.00
~
650.0Hz
0.01Hz
1.00Hz
60FH
○
F6.16~
F6.17
Reserved
-
-
-
610
~611H
*
F7 Group
:
Process Closloop PID Parameters
(
Toal 34
)
Code
Name
Setting Scope
Min Unit
Defaulted
Value
Address Change
F7.00
Close-loop PID control
0
:
Non Closeloop PID
control run
1
:
Closeloop PID control
run
1
0
700H
×
F7.01
Reference input method
0:Digital setting(F7.05
value)
1
:
Reserved
2
:
Reserved
3: LED keypad
potentiometer given
4
:
Reserved
1
0
701H
○
F7.02
Reserved
-
-
-
702H
*
F7.03
Input filter
0.01
~
50.00s
0.01s
0.5s
703H
○
F7.04
Feedback filter
0.01
~
50.00s
0.01s
0.5s
704H
○
F7.05
Digital referenceinput
0.00
~
10.00V
0.01
0.00
705H
○
F7.06
Reserved
-
-
-
706H
*
F7.07
Reserved
-
-
-
707H
*
F7.08
Min input
0.0%
~
F7.10
0.1%
0.0
708H
○
F7.09
Feedback of Min input
0.0
~
100.0%
0.1%
0.0%
709H
○
F7.10
Max input
F7.08
~
100.0%
0.1%
100.0%
70AH
○
F7.11
Feedback of Max input
0.0
~
100.0%
0.1%
100.0%
70BH
○
F7.12
Proportional gain Kp
0.000
~
9.999
0.001
0.050
70CH
○
F7.13
Integral gain Ki
0.000
~
9.999
0.001
0.050
70DH
○
F7.14
Sampling cycle Ts
0.01
~
50.00s
0.01s
0.50s
70EH
○
F7.15
Error limit
0.0
~
20.0%
0.1%
2.0%
70FH
○
F7.16
Closed-loop regulation
characteristics
0
:
Positive logic
1
:
Negative logic
1
0
710H
×
F7.17~
F7.28
Reserved
-
-
-
711H~
71CH
*
F7.29
PID Feedback break line
detection
0.0
~
80.0%
0.1%
0.0%
71DH
×
F7.30
PID Feedback break line
detection time
0
~
999.9s
1s
0.0s
71EH
×
F7.31~
F7.33
Reserved
-
-
-
71FH~
721H
*