16
Code
Function Name
Setting Range
Setting During
Operation
(allowed or not)
Change During
Operation
(allowed or not)
Default
Setting
Ot
he
rs
b088
Restart mode after FRS
00 (starting with 0 Hz) /
01 (starting with matching frequency) /
02 (starting with active matching frequency)
×
○
00
b089
Automatic carrier frequency reduction
00 (disabled) /
01 (enabled [output current controlled]) /
02 (enabled [fin temperature controlled])
×
×
01
b090
Dynamic braking usage ratio
0.0 to 100.0 [%]
×
○
0.0
b091
Stop mode selection
00 (deceleration until stop) /
01 (free-run stop)
×
○
00
b092
Cooling fan control
00 (fan always ON) /
01 (ON fan only during inverter operation
[including 5 minutes after power-on and power-off]
) /
02 (fin temperature controlled)
×
○
01
b093
Accumulated time clear of the cooling fan
00 (count) / 01 (clear)
×
×
00
b094
Initialization target data setting
00 (All parameters) /
01 (All parameters except in/output terminals and communication) /
02 (Uxxx) /
03 (expect Uxxx)
×
×
00
b095
Dynamic braking control (BRD) selection
00 (disabled) /
01 (enabled [disabled while the inverter is stopped]) /
02 (enabled [enabled also while the inverter is stopped])
×
○
01
b096
BRD activation level
330 to 380 / 660 to 760 [V]
×
○
360 / 720
Fr
ee
-s
et
ti
ng V
/f p
at
te
rn
b100
Free-setting V/ F freq. (1)
0. to b102 [Hz]
×
×
0.
b101
Free-setting V/ F volt. (1)
0.0 to 800.0 [V]
×
×
0.0
b102
Free-setting V/ F freq. (2)
0. to b104 [Hz]
×
×
0.
b103
Free-setting V/ F volt. (2)
0.0 to 800.0 [V]
×
×
0.0
b104
Free-setting V/ F freq. (3)
0. to b106 [Hz]
×
×
0.
b105
Free-setting V/ F volt. (3)
0.0 to 800.0 [V]
×
×
0.0
b106
Free-setting V/ F freq. (4)
0. to b108 [Hz]
×
×
0.
b107
Free-setting V/ F volt. (4)
0.0 to 800.0 [V]
×
×
0.0
b108
Free-setting V/ F freq. (5)
0. to b110 [Hz]
×
×
0.
b109
Free-setting V/ F volt. (5)
0.0 to 800.0 [V]
×
×
0.0
b110
Free-setting V/ F freq. (6)
0. to b112 [Hz]
×
×
0.
b111
Free-setting V/ F volt. (6)
0.0 to 800.0 [V]
×
×
0.0
b112
Free-setting V/ F freq. (7)
0. to 400 ( to 1000) [Hz]
×
×
0.
b113
Free-setting V/ F volt. (7)
0.0 to 800.0 [V]
×
×
0.0
Ot
he
rs
b120
Brake control enable
00 (disabled) / 01 (enabled)
×
○
00
b121
Brake Wait Time for Release
0.00 to 5.00 [s]
×
○
0.00
b122
Brake Wait Time for Acceleration
0.00 to 5.00 [s]
×
○
0.00
b123
Brake Wait Time for Stopping
0.00 to 5.00 [s]
×
○
0.00
b124
Brake Wait Time for Confirmation
0.00 to 5.00 [s]
×
○
0.00
b125
Brake release freq. setting
0.00 to 99.99 / 100.0 to 400.0 [Hz]
×
○
0.00
b126
Brake release current setting
Set range: 0 to 200% of inverter rated current [A]
×
○
Rated current
of inverter
b127
Braking frequency
0.00 to 99.99 / 100.0 to 400.0 [Hz]
×
○
0.00
b130
Over-voltage LADSTOP enable
00 (disabled) / 01 (enabled) / 02 (enabled with acceleration)
×
○
00
b131
Over-voltage LADSTOP level
330 to 395 / 660 to 790 [V]
×
○
380 / 760
b132
DC bus AVR constant setting
0.10 to 30.00 (s)
×
○
1.00
b133
DC bus AVR for decel. Proportional-gain
0.00 to 5.00
○
○
0.20
b134
DC bus AVR for decel. Integral-time
0.0 to 150.0 [s]
○
○
1.0
b145
GS input performance selection
00 (non Trip) / 01 (Trip)
×
○
00
b150
Panel Display selection
d001 to d060
○
○
001
b160
1st parameter of Double Monitor
d001 to d030
○
○
001
b161
2nd parameter of Double Monitor
d001 to d030
○
○
002
b163
Data change mode selection of d001 and d007
00 (disabled) / 01 (enabled)
○
○
00
b164
Automatic return to the initial display
00 (disabled) / 01 (enabled)
○
○
00
b165
Action selection in case of external operator disconnection
00 (tripping) /
01 (tripping after decelerating and stopping the motor) /
02 (ignoring errors) /
03 (stopping the motor after free-running) /
04 (decelerating and stopping the motor)
○
○
02
b171
Inverter mode selection
00 (disabled) / 01 (IM enabled)
×
×
00
b180
Initialization trigger
00 (disabled) / 01 (enabled)
×
×
00
Pa
ss
wo
rd
b190
Password A setting
0 (disabled) / 0001 to FFFF (enabled)
×
×
0000
b191
Password A for authentication
0000 to FFFF
×
×
0000
b192
Password B setting
0 (disabled) / 0001 to FFFF (enabled)
×
×
0000
b193
Password B for authentication
0000 to FFFF
×
×
0000
Function List
[
○
= Allowed × = Not parmitted
]