14
Code
Function Name
Setting Range
Setting During
Operation
(allowed or not)
Change During
Operation
(allowed or not)
Default
Setting
O
pe
ra
ti
on
m
ode
a
nd
A
cce
l.
/D
ece
l.
fu
nc
ti
on
A085
Operation mode selection
00 (normal operation), / 01 (energy-saving operation)
×
×
00
A086
Energy saving mode tuning
0.0 to 100.0 [%]
○
○
50.0
A092
Acceleration (2) time setting
0.01 to 99.99 / 100.0 to 999.9 / 1000. to 3600. [s]
○
○
10.00
A292
Acceleration (2) time setting, 2nd motor
0.01 to 99.99 / 100.0 to 999.9 / 1000. to 3600. [s]
○
○
10.00
A093
Deceleration (2) time setting
0.01 to 99.99 / 100.0 to 999.9 / 1000. to 3600. [s]
○
○
10.00
A293
Deceleration (2) time setting, 2nd motor
0.01 to 99.99 / 100.0 to 999.9 / 1000. to 3600. [s]
○
○
10.00
A094
Select method to switch to Acc2 / Dec2 profile
00 (switching by 2CH terminal) / 01 (switching by setting) /
02 (Forward and reverse)
×
×
00
A294
Select method to switch to Acc2 / Dec2 profile, 2nd motor
×
×
00
A095
Acc1 to Acc2 frequency transition point
0.00 to 99.99 / 100.0 to 400.0 [Hz]
×
×
0.00
A295
Acc1 to Acc2 frequency transition point, 2nd motor
0.00 to 99.99 / 100.0 to 400.0 [Hz]
×
×
0.00
A096
Dec1 to Dec2 frequency transition point
0.00 to 99.99 / 100.0 to 400.0 [Hz]
×
×
0.00
A296
Dec1 to Dec2 frequency transition point, 2nd motor
0.00 to 99.99 / 100.0 to 400.0 [Hz]
×
×
0.00
A097
Acceleration curve selection
00 (linear) / 01 (S curve) / 02 (U curve) / 03 (inverted-U curve) / 04 (EL-S curve)
×
×
01
A098
Deceleration curve selection
×
×
01
Ex
te
rn
al
fr
eq
ue
nc
y
tun
ing
A101
[OI]-[L] input active range start frequency
0.00 to 99.99 / 100.0 to 400.0 [Hz]
×
○
0.00
A102
[OI]-[L] input active range end frequency
0.00 to 99.99 / 100.0 to 400.0 [Hz]
×
○
0.00
A103
[OI]-[L] input active range start current
0 to 100 [%]
×
○
20
A104
[OI]-[L] input active range end voltage
0 to 100 [%]
×
○
100
A105
[OI]-[L] input start frequency enable
00 (A101) / 01 (0Hz)
×
○
00
Acce
l./
De
ce
l. c
ur
ve
A131
Acceleration curve constant setting (for S, U, Inverse U)
01 to 10
×
○
02
A132
Deceleration curve constant setting (for S, U, Inverse U)
01 to 10
×
○
02
O
pe
ra
ti
on t
ar
ge
t
fr
eq
ue
ncy
A141
A input select for calculate function
00 (digital operator) / 01 (keypad potentiometer) / 02 (input via O) / 03 (input via OI) /
04 (external communication) / 05 (option) / 07 (pulse train frequency input)
×
○
02
A142
B input select for calculate function
×
○
03
A143
Calculation symbol
00 (A141 + A142) / 01 (A141 - A142) / 02 (A141 × A142)
×
○
00
A145
ADD frequency
0.00 to 99.99 / 100.0 to 400.0 [Hz]
×
○
0.00
A146
ADD direction select
00 (frequency c A145) / 01 (frequency command - A145)
×
○
00
Ac
cele
ra
tio
n
and
dece
le
ra
tion
A150
Curvature of EL-S-curve at the start of acceleration
0 to 50 [%]
×
×
10
A151
Curvature of EL-S-curve at the end of acceleration
0 to 50 [%]
×
×
10
A152
Curvature of EL-S-curve at the start of deceleration
0 to 50 [%]
×
×
10
A153
Curvature of EL-S-curve at the end of deceleration
0 to 50 [%]
×
×
10
Ot
he
rs
A154
Deceleration stop frequency setting
0.00 to 99.99 / 100.0 to 400.0 [Hz]
×
○
0.00
A155
Deceleration stop time setting
0.0 to 60.0 [s]
×
○
0.0
PID
co
nt
rol
A156
PID sleep function action threshold
0.00 to 99.99 / 100.0 to 400.0 [Hz]
×
○
0.00
A157
PID sleep function action delay time
0.0 to 25.5 [s]
×
○
0.0
Fr
equ
en
cy
tr
im
mi
ng
A161
[VR] input active range start frequency
0.00 to 99.99 / 100.0 to 400.0 [Hz]
×
○
0.00
A162
[VR] input active range end frequency
0.00 to 99.99 / 100.0 to 400.0 [Hz]
×
○
0.00
A163
[VR] input active range start current
0 to 100 [%]
×
○
0
A164
[VR] input active range end voltage
0 to 100 [%]
×
○
100
A165
[VR] input start frequency enable
00 (A161) / 01 (0Hz)
×
○
01
Re
st
ar
t a
ft
er i
ns
ta
nt
an
eo
us p
ow
er f
ai
lu
re
b001
Selection of automatic restart mode
00 (tripping) / 01 (starting with 0 Hz) / 02 (starting with matching frequency) /
03 (tripping after deceleration and stopping with matching frequency) /
04 (restarting with active matching frequency)
×
○
00
b002
Allowable under-voltage power failure time
0.3 to 25.0 [s]
×
○
1.0
b003
Retry wait time before motor restart
0.3 to 100.0 [s]
×
○
1.0
b004
Instantaneous power failure / under-voltage trip alarm enable 00 (disabled) / 01 (enabled) / 02 (disabled during stopping and decelerating to stop)
×
○
00
b005
Number of restarts on power failure /
under-voltage trip events
00 (16 times) / 01 (unlimited)
×
○
00
b007
Restart frequency threshold
0.00 to 99.99 / 100.0 to 400.0 [Hz]
×
○
0.00
b008
Selection of retry after tripping
00 (tripping) / 01 (starting with 0 Hz) / 02 (starting with matching frequency) /
03 (tripping after deceleration and stopping with matching frequency) /
04 (restarting with active matching frequency)
×
○
00
b010
Selection of retry count after undervoltage
1 to 3 [times]
×
○
3
b011
Start freq. to be used in case of freq. matching restart
0.3 to 100.0 [s]
×
○
1.0
Ele
ct
ron
ic
T
her
m
al
b012
Level of electronic thermal setting
Set a level between 20% and 100% for the rated inverter current [A]
×
○
Rated current
of inverter
b212
Level of electronic thermal setting, 2nd motor
Set a level between 20% and 100% for the rated inverter current [A]
×
○
Rated current
of inverter
b013
Electronic thermal characteristic
00 (reduced-torque characteristic) / 01 (constant-torque characteristic) /
02 (free setting)
×
○
01
b213
Electronic thermal characteristic, 2nd motor
×
○
01
b015
Free setting, electronic thermal frequency (1)
0 to "electronic thermal frequency (2)" [Hz]
×
○
0
b016
Free setting, electronic thermal current (1)
Range is 0 to inverter rated current Amps [A]
×
○
0.00
b017
Free setting, electronic thermal frequency (2)
"electronic thermal frequency (1)" to "electronic thermal frequency (3)" [Hz]
×
○
0
b018
Free setting, electronic thermal current (2)
Range is 0 to inverter rated current Amps [A]
×
○
0.00
b019
Free setting, electronic thermal frequency (3)
"electronic thermal frequency (2)" to 400 [Hz]
×
○
0
b020
Free setting, electronic thermal current (3)
Range is 0 to inverter rated current Amps [A]
×
○
0.00
Function List
[
○
= Allowed × = Not parmitted
]
Stöwer Antriebstechnik GmbH, Enneststrasse 3, 51702 Bergneustadt, tel: 02261-40970, Fax: 02261-41309