6
*1: The applicable motor refers to Hitachi standard 3-phase motor (4p). When using other motors, care must be taken to prevent the rated motor current (50/60Hz) from exceeding the rated output current of the inverter.
*2: The output voltage varies as the main supply voltage varies (except when using the AVR function). In any case, the output voltage cannot exceed the input power supply voltage.
Models WJ200-
001LF
002LF
004LF
007LF
015LF
022LF
037LF
055LF
075LF
110LF
150LF
Applicable motor size *
1
kW
VT
0.2
0.4
0.75
1.1
2.2
3.0
5.5
7.5
11
15
18.5
CT
0.1
0.2
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
HP
VT
1/4
1/ 2
1
1.5
3
4
7.5
10
15
20
25
CT
1/ 8
1/4
1/ 2
1
2
3
5
7.5
10
15
20
Rated capacity (kVA)
200V
VT
0.4
0.6
1.2
2.0
3.3
4.1
6.7
10.3
13.8
19.3
23.9
CT
0.2
0.5
1.0
1.7
2.7
3.8
6.0
8.6
11.4
16.2
20.7
240V
VT
0.4
0.7
1.4
2.4
3.9
4.9
8.1
12.4
16.6
23.2
28.6
CT
0.3
0.6
1.2
2.0
3.3
4.5
7.2
10.3
13.7
19.5
24.9
Input
Rating
Rated input voltage (V)
3-phase: 200V-15% to 240V +10%, 50 / 60Hz ±5%
Rated input current (A)
VT
1.2
1.9
3.9
7.2
10.8
13.9
23.0
37.0
48.0
68.0
72.0
CT
1.0
1.6
3.3
6.0
9.0
12.7
20.5
30.8
39.6
57.1
62.6
Output
Rating
Rated output voltage (V) *
2
3-phase: 200 to 240V (proportional to input voltage)
Rated output current (A)
VT
1.2
1.9
3.5
6.0
9.6
12.0
19.6
30.0
40.0
56.0
69.0
CT
1.0
1.6
3.0
5.0
8.0
11.0
17.5
25.0
33.0
47.0
60.0
Minimum value of resistor (Ω)
100
100
100
50
50
35
35
20
17
17
10
Weight
kg
1.0
1.0
1.1
1.2
1.6
1.8
2.0
3.3
3.4
5.1
7.4
lb
2.2
2.2
2.4
2.6
3.5
4.0
4.4
7.3
7.5
11.2
16.3
Models WJ200-
001SF
002SF
004SF
007SF
015SF
022SF
Applicable motor size *
1
kW
VT
0.2
0.4
0.55
1.1
2.2
3.0
CT
0.1
0.2
0.4
0.75
1.5
2.2
HP
VT
1/4
1/2
3/4
1.5
3
4
CT
1/8
1/4
1/2
1
2
3
Rated capacity (kVA)
200V
VT
0.4
0.6
1.2
2.0
3.3
4.1
CT
0.2
0.5
1.0
1.7
2.7
3.8
240V
VT
0.4
0.7
1.4
2.4
3.9
4.9
CT
0.3
0.6
1.2
2.0
3.3
4.5
Input
Rating
Rated input voltage (V)
1-phase: 200V-15% to 240V +10%, 50 / 60Hz ±5%
Rated input current (A)
VT
2.0
3.6
7.3
13.8
20.2
24.0
CT
1.3
3.0
6.3
11.5
16.8
22.0
Output
Rating
Rated output voltage (V) *
2
3-phase: 200 to 240V (proportional to input voltage)
Rated output current (A)
VT
1.2
1.9
3.5
6.0
9.6
12.0
CT
1.0
1.6
3.0
5.0
8.0
11.0
Minimum value of resistor (Ω)
100
100
100
50
50
35
Weight
kg
1.0
1.0
1.1
1.6
1.8
1.8
lb
2.2
2.2
2.4
3.5
4.0
4.0
Models WJ200-
004HF
007HF
015HF
022HF
030HF
040HF
055HF
075HF
110HF
150HF
Applicable motor size *
1
kW
VT
0.75
1.5
2.2
3.0
4.0
5.5
7.5
11
15
18.5
CT
0.4
0.75
1.5
2.2
3.0
4.0
5.5
7.5
11
15
HP
VT
1
2
3
4
5
7.5
10
15
20
25
CT
1/2
1
2
3
4
5
7.5
10
15
20
Rated capacity (kVA)
200V
VT
1.3
2.6
3.5
4.5
5.7
7.3
11.5
15.1
20.4
25.0
CT
1.1
2.2
3.1
3.6
4.7
6.0
9.7
11.8
15.7
20.4
240V
VT
1.7
3.4
4.4
5.7
7.3
9.2
14.5
19.1
25.7
31.5
CT
1.4
2.8
3.9
4.5
5.9
7.6
12.3
14.9
19.9
25.7
Input
Rating
Rated input voltage (V)
3-phase: 380V-15% to 480V +10%, 50 / 60Hz ±5%
Rated input current (A)
VT
2.1
4.3
5.9
8.1
9.4
13.3
20.0
24.0
38.0
44.0
CT
1.8
3.6
5.2
6.5
7.7
11.0
16.9
18.8
29.4
35.9
Output
Rating
Rated output voltage (V) *
2
3-phase: 380 to 480V (proportional to input voltage)
Rated output current (A)
VT
2.1
4.1
5.4
6.9
8.8
11.1
17.5
23.0
31.0
38.0
CT
1.8
3.4
4.8
5.5
7.2
9.2
14.8
18.0
24.0
31.0
Minimum value of resistor (Ω)
180
180
180
100
100
100
70
70
70
35
Weight
kg
1.5
1.6
1.8
1.9
1.9
2.1
3.5
3.5
4.7
5.2
lb
3.3
3.5
4.0
4.2
4.2
4.6
7.7
7.7
10.4
11.5
3-phase 200V class
1-phase 200V class
3-phase 400V class
Standard Specifications
Stöwer Antriebstechnik GmbH, Enneststrasse 3, 51702 Bergneustadt, tel: 02261-40970, Fax: 02261-41309