15
Code
Function Name
Setting Range
Setting During
Operation
(allowed or not)
Change During
Operation
(allowed or not)
Default
Setting
O
ve
rlo
ad
r
es
tr
ic
tio
n
b021
Overload restriction operation mode
00 (disabled) / 01 (enabled during acceleration and constant-speed operation) /
02 (enabled during constant-speed operation) /
03 (enabled during acceleration and constant-speed operation [speed increase at regeneration])
×
○
01
b221
Overload restriction operation mode, 2nd motor
×
○
01
b022
Overload restriction level setting
Set a level between 20% and 200% / 150% for the rated inverter current [A] (CT/ VT)
×
○
150% of
Rated current
b222
Overload restriction level setting, 2nd motor
×
○
b023
Deceleration rate at overload restriction
0.1 to 999.9 / 1000. to 3000. [s]
×
○
1.0
b223
Overload restriction operation mode, 2nd motor
0.1 to 999.9 / 1000. to 3000. [s]
×
○
1.0
b024
Overload restriction operation mode 2
00 (disabled) / 01 (enabled during acceleration and constant-speed operation)/
02 (enabled during constant-speed operation) /
03 (enabled during acceleration and constant-speed operation [speed increase at regeneration])
×
○
01
b025
Overload restriction level 2 setting
Set a level between 20% and 200% / 150% for the rated inverter current [A] (CT/ VT)
×
○
150% of
Rated current
b026
Deceleration rate 2 at overload restriction
0.1 to 999.9 / 1000. to 3000. [s]
×
○
1.0
b027
OC suppression selection
00 (disabled) / 01 (enabled)
×
○
01
b028
Current level of active freq. matching restart setting
Set a level between 20% and 200% / 150% for the rated inverter current [A] (CT/ VT)
×
○
Rated current
of inverter
b029
Deceleration rate of frequency matching restart setting
0.1 to 999.9 / 1000. to 3000. [s]
×
○
0.5
b030
Start freq. to be used in case of active freq. Matching restart 00 (frequency at the last shutoff) / 01 (maximum frequency) / 02 (set frequency)
×
○
00
Lo
ck
b031
Software lock mode selection
00 (all parameters except b031 are locked when [SFT] terminal is ON) /
01 (all parameters except b031 and output frequency F001 are locked when [SFT] terminal is ON) /
02 (all parameters except b031 are locked) /
03 (all parameters except b031 and output frequency F001 are locked) /
10 (High level access including b031)
×
○
01
Ot
he
rs
b033
Motor cable length parameter
5 to 20
○
○
10
b034
Run / power ON warning time
0 to 9999. (0 to 99990 [hr ]) / 1000 to 6553 (100000 to 655350 [hr ])
×
○
0
b035
Rotation direction restriction
00 (Enable for both dir) / 01 (Enable for forward only) / 02 (Enable for reverse only)
×
×
00
b036
Reduced voltage start selection
0 (minimum reduced voltage start time) to 255 (maximum reduced voltage start time)
×
○
2
b037
Function code display restriction
0 (full display) / 1 (function-specific display) / 2 (user setting) /
3 (data comparison display) / 4 (basic display) / 5 (monitor display)
×
○
04
b038
Initial-screen selection
000 (Func. code that SET key pressed last displayed) /
001 to 060 (d001 to d060) / 201 (F001) /
202 (Screen displayed when the STR key was pressed last)
×
○
001
b039
Automatic user parameter setting
00 (disabled) / 01 (enabled)
×
○
00
Tor
que
li
mi
t
b040
Torque limit selection
00 (quadrant-specific setting) / 01 (switching by terminal) / 02 (O input)
×
○
00
b041
l
b044
Torque limit (1) – (4)
0 to 200 [%] / no
×
○
200
b045
Torque LAD STOP selection
00 (disabled) / 01 (enabled)
×
○
00
b046
Reverse run protection
00 (disabled) / 01 (enabled)
×
○
01
Ot
he
rs
b049
Dual Rating Selection
00 (CT mode) / 01 (VT mode)
×
×
00
N
on
st
op
op
er
at
ion
a
t
mome
nt
ar
y
powe
r f
ai
lu
re
b050
Selection of the nonstop operation
00 (disabled) / 01 (enabled) /
02 (nonstop operation at momentary power failure [no restoration]) /
03 (nonstop operation at momentary power failure [restoration to be done])
×
×
00
b051
Nonstop operation start voltage setting
0.0 to 999.9 / 1000. [V]
×
×
220 / 440
b052
OV-LAD Stop level of nonstop operation setting
0.0 to 999.9 / 1000. [V]
×
×
360 / 720
b053
Deceleration time of nonstop operation setting
0.1 to 999.9 / 1000. to 3600. [s]
×
×
1.00
b054
Frequency width of quick deceleration setting
0.00 to 10.00 [Hz]
×
×
0.00
W
indo
w
co
m
pa
ra
tor
b060
Maximum-limit level of window comparators O
0 to 100 [%]
○
○
100
b061
Minimum-limit level of window comparators O
0 to 100 [%]
○
○
0
b062
Hysteresis width of window comparators O
0 to 10 [%]
○
○
0
b063
Maximum-limit level of window comparators OI
0 to 100 [%]
○
○
100
b064
Minimum-limit level of window comparators OI
0 to 100 [%]
○
○
0
b065
Hysteresis width of window comparator (OI)
0 to 10 [%]
○
○
0
Ot
he
rs
b070
Operation level at O disconnection
0 to 100 [%] / no
×
○
no
b071
Operation level at OI disconnection
0 to 100 [%] / no
×
○
no
b075
Ambient temperature
-10 to 50 [
º
C]
○
○
40
b078
Watt-hour reset
00 (OFF) / 01 (ON)
○
○
00
b079
Watt-hour display gain setting
1 to 1000
○
○
1
b082
Start frequency adjustment
0.10 to 9.99 [Hz] ( to 200Hz)
×
○
0.50
b083
Carrier frequency setting
2.0 to 15.0 [kHz]
×
○
2.0
b084
Initialization mode (parameters or trip history)
00 (disabled) / 01 (clearing the trip history) / 02 (initializing the data) /
03 (clearing the trip history and initializing the data) /
04 (clearing the trip history and initializing the data and EzSQ program)
×
×
00
b085
Country for initialization
00 / 01
×
×
00
b086
Frequency scaling conversion factor
0.01 to 99.99
○
○
1.00
b087
STOP key enable
00 (enabled) /
01 (disabled) / 02 (disabled only stop)
×
○
00
Function List
[
○
= Allowed × = Not parmitted
]
Stöwer Antriebstechnik GmbH, Enneststrasse 3, 51702 Bergneustadt, tel: 02261-40970, Fax: 02261-41309