Setting
M
on
it
or
m
ode
d001
Output frequency monitoring
0.00 to 99.99 / 100.0 to 400.0 [Hz]
○
○
—
d002
Output current monitoring
0.0 to 655.3 [A]
—
—
—
d003
Rotation direction minitoring
F (Forward) / o (Stop) / r (Reverce)
—
—
—
d004
Process variable (PV), PID feedback monitoring
0.00 to 99.99 / 100.0 to 999.9 / 1000. to 9999. / 1000 to 9999 (10000 to 99990) /
100 to 999 (100000 to 999000)
—
—
—
d005
Intelligent input terminal status
(Example)
7, 5, 3, 1: ON
6, 4, 2 : OFF
—
—
—
d006
Intelligent output terminal status
(Example)
11: ON
AL, 12 : OFF
—
—
—
d007
Scaled output frequency monitoring
0.00 to 99.99 / 100.0 to 999.9 / 1000. to 9999. / 1000 to 3999
○
○
—
d008
Actual-frequency monitoring
-400. to -100. / -99.9 to -10.0 / -9.99 to -0.00 / 0.00 to 99.99 / 100.0 to 400.0 [Hz]
—
—
—
d009
Torque command monitoring
-200 to +200 [%]
—
—
—
d010
Torque bias monitoring
-200 to +200 [%]
—
—
—
d012
Torque monitoring
-200 to +200 [%]
—
—
—
d013
Output voltage monitoring
0.0 to 600.0 [V]
—
—
—
d014
Power monitoring
0.0 to 999.9 [kW]
—
—
—
d015
Cumulative power monitoring
0.0 to 999.9 / 1000. to 9999. / 1000 to 9999 (10000 to 99990) /
100 to 999 (100000 to 999000)
—
—
—
d016
Cumulative operation RUN time monitoring
0. to 9999. / 1000 to 9999 (10000 to 99990) / 100 to 999 (100000 to 999000) [hr]
—
—
—
d017
Cumulative power-on time monitoring
0. to 9999. / 1000 to 9999 (10000 to 99990) / 100 to 999 (100000 to 999000) [hr]
—
—
—
d018
Heat sink temperature monitoring
-20.0 to 150.0 [ ºC]
—
—
—
d022
Life-check monitoring
1: Capacitor on
main circuit board
2: cooling-fan
—
—
—
d023
EzSQ program counter
0 to 1024
—
—
—
d024
EzSQ program number
0000 to 9999
—
—
—
d025
User monitor 1
-2147483647 to 2147483647
—
—
—
d026
User monitor 2
-2147483647 to 2147483647
—
—
—
d027
User monitor 3
-2147483647 to 2147483647
—
—
—
d029
Position setting monitor
-268435455 to 268435455
—
—
—
d030
Position feedback monitor
-268435455 to 268435455
—
—
—
d050
Dual monitor
Displays two different data configured in b160 and b161.
—
—
—
d060
Inverter mode monitor
Displays currently selected inverter mode : I-C / I-V
—
—
—
d080
Trip Counter
0 to 65535
—
—
—
d081
l
d086
Trip info. 1–6 (factor)
Factor code
—
—
—
d090
Warning monitor
Warning code
—
—
—
d102
DC voltage monitoring (across P and N)
0.0 to 999.9 / 1000. [V]
—
—
—
d103
BRD load factor monitoring
0.0 to 100.0 [%]
—
—
—
d104
Electronic thermal overload monitoring
0.0 to 100.0 [%]
—
—
—
Se
tt
ing
m
ode
F001
Output frequency setting
0 / "start frequency" to "maximum frequency" [Hz]
○
○
0.00
F002
Acceleration (1) time setting
0.01 to 99.99 / 100.0 to 999.9 / 1000. to 3600. [s]
○
○
10.00
F202
Acceleration (1) time setting, 2nd motor
0.01 to 99.99 / 100.0 to 999.9 / 1000. to 3600. [s]
○
○
10.00
F003
Deceleration (1) time setting
0.01 to 99.99 / 100.0 to 999.9 / 1000. to 3600. [s]
○
○
10.00
F203
Deceleration (1) time setting, 2nd motor
0.01 to 99.99 / 100.0 to 999.9 / 1000. to 3600. [s]
○
○
10.00
F004
Keypad Run key routing
00 (Foward) / 01 (Reverce)
×
×
00
B
as
ic s
et
tin
gs
A001
Frequency source setting
00 (keypad potentiometer) / 01 (control circuit terminal block) / 02 (digital operator) /
03 (Modbus) / 04 (option) / 06 (pulse train input) / 07 (easy sequence) /
10 (operation function result)
×
×
02
A201
Frequency source setting, 2nd motor
×
×
02
A002
Run command source setting
01 (control circuit terminal block) / 02 (digital operator) /
03 (Modbus) / 04 (option)
×
×
02
A202
Run command source setting, 2nd motor
×
×
02
A003
Base frequency setting
30.0 to "maximum frequency (1st)" [Hz]
×
×
60
A203
Base frequency setting, 2nd motor
30.0 to "maximum frequency (2nd)" [Hz]
×
×
60
A004
Maximum frequency setting
"Base frequency (1st)" to 400.0 [Hz]
×
×
60
A204
Maximum frequency setting, 2nd motor
×
×
60
A
na
lo
g i
np
ut s
et
tin
g
A005
[AT] selection
00 (switching between O and OI terminals) / 02 (switching between O terminal and keypad potentiometer) /
03 (switching between OI terminal and keypad potentiometer)
×
×
00
A011
Pot./O-L input active range start frequency
0.00 to 99.99/100.0 to 400.0 [Hz]
×
○
0.00
A012
Pot./O-L input active range end frequency
0.00 to 99.99/100.0 to 400.0 [Hz]
×
○
0.00
A013
Pot./O-L input active range start voltage
0 to 100 [%]
×
○
0
A014
Pot./O-L input active range end voltage
0 to 100 [%]
×
○
100
A015
Pot./O-L input start frequency enable
00 (A011) / 01 (0Hz)
×
○
01
A016
External frequency filter time constant
1 to 30 / 31
×
○
8
A017
Easy sequence function selection
00 (disabled) / 01 (PRG terminal) / 02 (Always)
○
○
00
[
○
= Allowed × = Not parmitted
]
ON
OFF
ON
OFF
Lifetime expired
Normal
Function List
If a desired parameter is not displayed, check the setting of function "b037"(function code display restriction). To display all parameters, specify "00" for "b037".