13
Code
Function Name
Setting Range
Setting During
Operation
(allowed or not)
Change During
Operation
(allowed or not)
Default
Setting
M
ul
ti
spe
ed
and
J
ogg
ing
fr
eq
ue
ncy
s
et
ting
A019
Multi-speed operation selection
00 (Binary mode) / 01 (Bit mode)
×
×
00
A020
Multi-speed 0 setting
0.00 / "start frequency" to "maximum frequency (1st)" [Hz]
○
○
0.00
A220
Multi-speed 0 setting, 2nd motor
0.00 / "start frequency" to "maximum frequency (2nd)" [Hz]
○
○
0.00
A021
l
A035
Multi-speed 1 – 15 setting
0.00 / ”start frequency” to “maximum frequency” [Hz]
○
○
0.00
A038
Jog frequency setting
“start frequency” to 9.99 [Hz]
○
○
6.00
A039
Jog stop mode
00 (Free-run stop [invalid during run]) /
01 (Controlled deceleration [invalid during run]) /
02 (DC braking to stop [invalid during run]) /
03 (Free-run stop [valid during run])
04 (Controlled deceleration [valid during run])
05 (DC braking to stop [valid during run])
×
○
04
V
/f C
ha
ra
ct
er
is
ti
c
A041
Torque boost select
00 (manual torque boost) /
01 (automatic torque boost)
×
×
00
A241
Torque boost select, 2nd motor
×
×
00
A042
Manual torque boost value
0.0 to 20.0 [%]
○
○
1.0
A242
Manual torque boost value, 2nd motor
0.0 to 20.0 [%]
○
○
1.0
A043
Manual torque boost frequency adjustment
0.0 to 50.0 [%]
○
○
5.0
A243
Manual torque boost frequency adjustment, 2nd motor
0.0 to 50.0 [%]
○
○
5.0
A044
V/ f characteristic curve selection
00 (VC) / 01 (VP) / 02 (free V/ f) / 03 (SLV)
×
×
00
A244
V/ f characteristic curve selection, 2nd motor
00 (VC) / 01 (VP) / 02 (free V/ f) / 03 (SLV)
×
×
00
A045
V/ f gain setting
20 to 100 [%]
○
○
100
A245
V/ f gain setting, 2nd motor
20 to 100 [%]
○
○
100
A046
Voltage compensation gain for automatic torque boost
0 to 255
○
○
100
A246
Voltage compensation gain for automatic torque boost,
2nd motor
0 to 255
○
○
100
A047
Slip compensation gain for automatic torque boost
0 to 255
○
○
100
A247
Slip compensation gain for au tomatic tor que boos t ,
2nd motor
0 to 255
○
○
100
D
C b
ra
ki
ng
A051
DC braking enable
00 (disabled) / 01 (enabled) / 02 (output freq < [A052])
×
○
00
A052
DC braking frequency setting
0.00 to 60.00 [Hz]
×
○
0.50
A053
DC braking wait time
0.0 to 5.0 [s]
×
○
0.0
A054
DC braking force for deceleration
0 to 100 / 70 [%] (CT / VT)
×
○
50
A055
DC braking time for deceleration
0.0 to 60.0 [s]
×
○
0.5
A056
DC braking / edge or level detection for [DB] input
00 (edge operation) / 01 (level operation)
×
○
01
A057
DC braking force at start
0 to 100 / 70 [%] (CT / VT)
×
○
0
A058
DC braking time at start
0.0 to 60.0 [s]
×
○
0.0
A059
Carrier frequency during DC braking
2.0 to 15.0 / 10.0 [kHz] (CT / VT)
×
○
5.0
Fr
eq
uen
cy
u
pp
er
/l
ower
li
m
it
a
nd J
um
p f
re
qu
en
cy
A061
Frequency upper limit setting
0.00 / A062 to A004 [Hz]
×
○
0.00
A261
Frequency upper limit setting, 2nd motor
0.00 / A262 to A204 [Hz]
×
○
0.00
A062
Frequency lower limit setting
0.00 / b082 to A061 [Hz]
×
○
0.00
A262
Frequency lower limit setting, 2nd motor
0.00 / b082 to A261 [Hz]
×
○
0.00
A063
Jump (center) frequency setting 1
0.00 to 99.99 / 100.0 to 400.0 [Hz]
×
○
0.00
A064
Jump (hysteresis) frequency width setting 1
0.00 to 10.00 [Hz]
×
○
0.50
A065
Jump (center) frequency setting 2
0.00 to 99.99 / 100.0 to 400.0 [Hz]
×
○
0.00
A066
Jump (hysteresis) frequency width setting 2
0.00 to 10.00 [Hz]
×
○
0.50
A067
Jump (center) frequency setting 3
0.00 to 99.99 / 100.0 to 400.0 [Hz]
×
○
0.00
A068
Jump (hysteresis) frequency width setting 3
0.00 to 10.00 [Hz]
×
○
0.50
A069
Acceleration stop frequency setting
0.00 to 99.99 / 100.0 to 400.0 [Hz]
×
○
0.00
A070
Acceleration stop time setting
0.0 to 60.0 [s]
×
○
0.0
PI
D c
on
tr
ol
A071
PID enable
00 (disabled) / 01 (enabled) / 02 (enabled inverted-data output)
×
○
00
A072
PID proportional gain
0.00 to 25.00
○
○
1.00
A073
PID integral time constant
0.0 to 999.9 / 1000. to 3600. [s]
○
○
1.0
A074
PID derivative time constant
0.00 to 99.99 / 100.0 [s]
○
○
0.00
A075
PV scale conversion
0.01 to 99.99
×
○
1.00
A076
PV source setting
00 (input via OI) / 01 (input via O) / 02 (external communication) /
03 (pulse train frequency input) / 10 (operation result output)
×
○
00
A077
Reverse PID action
00 (OFF) / 01 (ON)
×
○
00
A078
PID output limit
0.0 to 100.0 [%]
×
○
0.0
A079
PID feed forward selection
00 (disabled) / 01 (O input) / 02 (OI input)
×
○
00
A
V
R f
un
ct
io
n
A081
AVR function select
00 (always on) / 01 (always off) / 02 (off during deceleration)
×
×
02
A281
AVR function select, 2nd motor
00 (always on) / 01 (always off) / 02 (off during deceleration)
×
×
02
A082
AVR voltage select
200 V class : 200 / 215 / 220 / 230 / 240 (V)
400 V class : 380 / 400 / 415 / 440 / 460 / 480 (V)
×
×
200 / 400
A282
AVR voltage select, 2nd motor
200 V class : 200 / 215 / 220 / 230 / 240 (V)
400 V class : 380 / 400 / 415 / 440 / 460 / 480 (V)
×
×
200 / 400
A083
AVR filter time constant
0.000 to 9.999 / 10.00 [s]
×
○
0.300
A084
AVR deceleration gain
50 to 200 [%]
×
○
100
Function List
[
○
= Allowed × = Not parmitted
]
Stöwer Antriebstechnik GmbH, Enneststrasse 3, 51702 Bergneustadt, tel: 02261-40970, Fax: 02261-41309