13. Troubleshooting
13-97
13.2.4 PI/O module troubleshooting
This section describes how to perform PI/O module troubleshooting.
13.2.4.1 Analog module troubleshooting
Perform analog module troubleshooting according to Table 13-43 and Table 13-44.
Table 13-43 Analog input module troubleshooting
Operational error
Check
Corrective action
Input data cannot be
correctly acquired.
Are there any problems with the analog input
installation?
Correct the installation.
Are there any mistakes in the terminal block
installation?
Correctly install the terminal block.
Are there any problems in the input cabling?
Correct the cabling.
Are there any mistakes in the grounding?
Correctly ground the system.
When mode 1 is specified, is the analog
module registered in the CPU module?
Use the tools to register the analog module
specified for mode 1.
Is the range of input data being exceeded?
Use the correct range of input data.
Errors other than the
above
Does the error persist, even after the above
corrective action has been taken?
Replace the relevant module.
Summary of Contents for S10VE
Page 1: ...User s Manual General Description SEE 1 001 A ...
Page 2: ...User s Manual General Description ...
Page 53: ...This page is intentionally left blank ...
Page 59: ...This page is intentionally left blank ...
Page 67: ...This page is intentionally left blank ...
Page 75: ...This page is intentionally left blank ...
Page 77: ...This page is intentionally left blank ...
Page 103: ...This page is intentionally left blank ...
Page 129: ...This page is intentionally left blank ...
Page 295: ...This page is intentionally left blank ...
Page 309: ...This page is intentionally left blank ...
Page 341: ...This page is intentionally left blank ...
Page 345: ...This page is intentionally left blank ...
Page 475: ...This page is intentionally left blank ...
Page 489: ...This page is intentionally left blank ...
Page 505: ......