6. Installation
6-4
6.4 Mounting clearances
To ensure normal operation of the S10VE, you must provide air apertures with air filters at the top and bottom
of the cabinet. You must also provide the clearances shown in Figure 6-4 between the cabinet and each unit.
When stacking multiple S10VE units or when a heat source is present beneath the S10VE unit, use a shield plate
or other means to eliminate the effect of the heat source. If your environment does not allow a shield plate or the
like to be added, you must carry out a test run of the system and make sure that the temperature does not exceed
55°C around any unit.
Figure 6-4 Unit mounting clearances
Notice
●
To avoid failure or malfunction, leave clearance of at least 100 mm between the cabinet (top and bottom
panels) and unit, and between each unit. If you are unable to provide 100 mm of clearance, make sure
that the intake air temperature will not exceed 55°C.
●
To avoid failure or malfunction, leave clearance of at least 50 mm between the cabinet (side panels) and
units. If you are unable to provide 50 mm of clearance, make sure that the intake air temperature will
not exceed 55°C.
At least
50 mm
At least
50 mm
At least 100 mm
At least 100 mm
At least 100 mm
Air outlet
Air intake
At least
50 mm
At least
50 mm
Cabinet
PR
SR
TX
RX
TX
LQE510-E OD.RING
PR
TR
RX
ERR
SR
TR
RX
ERR
CPL
No.
MODU
No.
U
L
RX
PR
SR
TX
RX
TX
LQE510-E OD.RING
PR
TR
RX
ERR
SR
TR
RX
ERR
CPL
No.
MODU
No.
U
L
RX
LQE770-E
D.NET
MODU
No.
MS
NS
CH0
CH1
CH0
CH1
LQE770-E
D.NET
MODU
No.
MS
NS
CH0
CH1
CH0
CH1
LQE540-E J.NET
N1
TX
RX
ER
N2
TR
RX
ERR
TYPE-M521
MODU
No.
BIT
RATE
TERM
A
B
SG
SHD
TERM
A
B
SG
SHD
FG
N1
N2
LQE540-E J.NET
N1
TX
RX
ER
N2
TR
RX
ERR
TYPE-M521
MODU
No.
BIT
RATE
TERM
A
B
SG
SHD
TERM
A
B
SG
SHD
FG
N1
N2
LQE260-E
ET.NET
RUN
ALARM
ERR
10BASE-T
100BASE-TX
CH 1
MAIN
/SUB
U
L
ST.No.
CH2
TX/RX
100M
10M
TX/RX
100M
10M
LQE950
RI/O-IF
RI/O
STOP
STOP
/RUN
SHD
PCsOK
100VAC
100VDC
SHD
SHD
TERM
150Ω
TERM
100Ω
SHD
FG
L
A
B
100VAC
100VDC
TERM
150Ω
TERM
100Ω
A
B
RI/O1
RI/O2
L
FG
ALARM
ET2
ET1
2
1
ACT
1
2
LINK
LQP600
CPU
RUN
STOP
ERR
STBY
RUN
LADDER
SET
ESC
L
R
UP
DWN
OC
OV
LQV410
PS
DC5V
GND
HITACHI
POWER
100-120VAC 144VA 50/60Hz
100-110VDC 132W
FG
H
+
N
-
OFF
ON
P
O
W
E
R
INPUT
100-120VAC
100-110VDC
警告
WARNING
感電危険触れるな
Hazardous voltage
will cause death or
severe injury
!
SERVICE
CHECK
Summary of Contents for S10VE
Page 1: ...User s Manual General Description SEE 1 001 A ...
Page 2: ...User s Manual General Description ...
Page 53: ...This page is intentionally left blank ...
Page 59: ...This page is intentionally left blank ...
Page 67: ...This page is intentionally left blank ...
Page 75: ...This page is intentionally left blank ...
Page 77: ...This page is intentionally left blank ...
Page 103: ...This page is intentionally left blank ...
Page 129: ...This page is intentionally left blank ...
Page 295: ...This page is intentionally left blank ...
Page 309: ...This page is intentionally left blank ...
Page 341: ...This page is intentionally left blank ...
Page 345: ...This page is intentionally left blank ...
Page 475: ...This page is intentionally left blank ...
Page 489: ...This page is intentionally left blank ...
Page 505: ......