3 Piping work and
refrigerant charge
79
SMGB0087 rev.0 - 12/2013
3
Line branch system
A
B
C
D
(mm)
Multi-kit model A
Multi-kit model B
Outdoor Unit
HP
Pipe Size (D)
IVX Premium
Series
IVX Standard
Series
IVX Premium
Series
IVX Standard
Series
Gas
Liquid
3 / 4 / 5 / 6
Ø15.88
Ø9.52
E-102SN(2/3)
E-102SN(2/3)
E-102SN(2/3)
E-102SN(2/3)
8
Ø25.40
Ø9.52(1)
E-162SN(2/3)
E-162SN(2/3)
E-102SN(2/3)
E-102SN(2/3)
10 /12
Ø25.40
Ø12.70
E-162SN(2/3)
E-162SN(2/3)
E-102SN(2/3)
E-102SN(2/3)
(1) In case that total pipe length from the outdoor to the farthest indoor unit exceeds of 70m in 8 HP unit, please use a Ø12.7 pipe as
a liquid pipe.
(mm)
Indoor Unit capacity
Pipe Size (C)
Gas
Liquid
≤ 1.5 HP
Ø12.70
Ø6.35
1.8 / 2.0 HP
Ø15.88
Ø6.35
> 2.3 HP
Ø15.88
Ø9.52
N O T E
Connections including Indoor Units 8 and 10 HP are not possible.
Summary of Contents for RAS-(2-6)HVNP1(E)
Page 2: ......
Page 4: ... II ...
Page 28: ......
Page 134: ...4 Electrical wiring 120 SMGB0087 rev 0 12 2013 4 7 3 RAS 3HVNP1E 1 230V 50Hz XEK01261_0 ...
Page 136: ...4 Electrical wiring 122 SMGB0087 rev 0 12 2013 4 7 4 RAS 4 6 HVNP1E 1 230V 50Hz XEK01262_1 ...
Page 138: ...4 Electrical wiring 124 SMGB0087 rev 0 12 2013 4 7 6 RAS 4 6 HNP1E 3N 400V 50Hz XEK01263_2 ...
Page 140: ...4 Electrical wiring 126 SMGB0087 rev 0 12 2013 4 7 7 RAS 4 6 HVNC1E 1 230V 50Hz XEK01264_4 ...
Page 142: ...4 Electrical wiring 128 SMGB0087 rev 0 12 2013 4 7 8 RAS 4 6 HNC1E 3N 400V 50Hz XEK01265_4 ...
Page 146: ...4 Electrical wiring 132 SMGB0087 rev 0 12 2013 4 7 12 RAS 12HN P C 3N 400V 50Hz 7T146440 ...
Page 148: ......
Page 204: ......
Page 220: ......
Page 332: ......
Page 353: ...9 Spare parts 339 SMGB0087 rev 0 12 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211D ...
Page 362: ......
Page 484: ......
Page 496: ......
Page 497: ......