8 Troubleshooting
269
SMGB0087 rev.0 - 12/2013
8
Are the power wires
passed through CT
(inverter element)?
No
Failure of inverter PCB.
Replace it.
No
Restart operation.
Yes
Check the
compressor
Normal
Check the compressor.
Replace if faulty.
Abnormal
Check transistor
module (*1)(*2)
Apply silicon to cover
entirely the space
Faulty inverter PCB.
Replace it.
Check the compressor
Is high pressure increased?
Check pressure and
refrigerant cycle
Check clogging for heat
exchanger
Check fan motor
* Refer to the item
“Cause of inverter
stoppage (24)”
for details.
Compressor stops
after few minutes.
(Itc=21)*
Compressor stops
immediately.
(Itc=1, 12)*
Turn OFF power,
disconnect U, V, W
from compressor
terminals and restart.
Does the protecting
function activate? *3)
Pass the power wires
through CT
Yes
No
Replace transistor and
inverter
Check inverter
PCB
Normal
Replace transistor module
Abnormal
Abnormal
Is the space
between the
transistor module and
radiation fins entirely
covered by silicon?
Normal
Yes
Is heat exchanger
of clogged?
Yes
Remove clogging or replace
heat exchanger
N O T E
• *1) Perform the high voltage discharge work by referring to the item
“8.4.7 Checking procedure for other parts”
, before
checking and replacing the inverter components.
• *2) Regarding replacing or checking method for inverter components, refer to item
“8.4.7 Checking procedure for other
parts”
.
• *3) Turn ON the number1 switch of the dip switch DSW1 on PCB2 (inverter) when restarting with disconnecting the
terminals of the compressor. After troubleshooting, turn OFF the number1 switch of the dip switch DSW1 on PCB2.
• When the alarm code “53” is indicated, the outdoor fan motor (DC motor) ensure that DC fan motor is checked accord-
ing to the item
“8.4.7 Checking procedure for other parts”
.
Summary of Contents for RAS-(2-6)HVNP1(E)
Page 2: ......
Page 4: ... II ...
Page 28: ......
Page 134: ...4 Electrical wiring 120 SMGB0087 rev 0 12 2013 4 7 3 RAS 3HVNP1E 1 230V 50Hz XEK01261_0 ...
Page 136: ...4 Electrical wiring 122 SMGB0087 rev 0 12 2013 4 7 4 RAS 4 6 HVNP1E 1 230V 50Hz XEK01262_1 ...
Page 138: ...4 Electrical wiring 124 SMGB0087 rev 0 12 2013 4 7 6 RAS 4 6 HNP1E 3N 400V 50Hz XEK01263_2 ...
Page 140: ...4 Electrical wiring 126 SMGB0087 rev 0 12 2013 4 7 7 RAS 4 6 HVNC1E 1 230V 50Hz XEK01264_4 ...
Page 142: ...4 Electrical wiring 128 SMGB0087 rev 0 12 2013 4 7 8 RAS 4 6 HNC1E 3N 400V 50Hz XEK01265_4 ...
Page 146: ...4 Electrical wiring 132 SMGB0087 rev 0 12 2013 4 7 12 RAS 12HN P C 3N 400V 50Hz 7T146440 ...
Page 148: ......
Page 204: ......
Page 220: ......
Page 332: ......
Page 353: ...9 Spare parts 339 SMGB0087 rev 0 12 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211D ...
Page 362: ......
Page 484: ......
Page 496: ......
Page 497: ......