refrigerant charge
86
SMGB0087 rev.0 - 12/2013
Additional refrigerant charge calculation method
Calculate the additional refrigerant charge amount according to the following steps:
Step 1: Additional refrigerant charge calculation for liquid piping (W
1
(kg))
Outdoor units have been charged with refrigerant for 30m (20m for RAS-3HVNC) of actual piping length, an additional
refrigerant charged is required in systems with actual piping length longer.
a.
For all UTOPIA units except RAS-(8-12)HN(P/C)(E)
Use the following formula:
W
1
= (L-30) x P (*)
L: Total piping length (m)
P: Additional refrigerant charge (g/m)
N O T E
(*): In case of RAS-(2-2.5)HVNP units installed in 2 indoor units system, the unit is considered to be charged with refrige-
rant for 0 m. In these cases, the formula for calculating the additional refrigerant charge is:
W
1
= (L-0) x P
In case of RAS-3HVNC, the unit is charged with refrigerant for 20 m. In these cases, the formula for calculating the addi-
tional refrigerant charge is:
W
1
= (L-20) x P
Example:
A. 30 m.
B. 8 m.
C. 8 m.
• Chargeless Length
ℓ
: for RAS-4HVNP1E is 30 m according to the
previous table.
• Additional Correction Value
P
: for RAS-4HVNP1E, “60” according
to the previous table.
• Additional Charge amount
W
will be:
W = (L-ℓ) x P
Example: W
1
= (46-30) x 60=
960 (g)
b.
For UTOPIA units RAS-(8-12)HN(P/C)(E)
The additional refrigerant charge for RAS-(8-12)HN(P/C)(E) units must be calculated by multiplying the total piping length
of each diameter per its calculation factor according to the following table. The result is the additional refrigerant charge for
liquid piping. (Fill the table with the values)
Pipe size (mm)
Additional refrigerant charge factor (kg/m)
Ø15.88
x 0.19
Ø12.7
x 0.12
Ø9.52
x 0.065
Ø6.35
x 0.065
Summary of Contents for RAS-(2-6)HVNP1(E)
Page 2: ......
Page 4: ... II ...
Page 28: ......
Page 134: ...4 Electrical wiring 120 SMGB0087 rev 0 12 2013 4 7 3 RAS 3HVNP1E 1 230V 50Hz XEK01261_0 ...
Page 136: ...4 Electrical wiring 122 SMGB0087 rev 0 12 2013 4 7 4 RAS 4 6 HVNP1E 1 230V 50Hz XEK01262_1 ...
Page 138: ...4 Electrical wiring 124 SMGB0087 rev 0 12 2013 4 7 6 RAS 4 6 HNP1E 3N 400V 50Hz XEK01263_2 ...
Page 140: ...4 Electrical wiring 126 SMGB0087 rev 0 12 2013 4 7 7 RAS 4 6 HVNC1E 1 230V 50Hz XEK01264_4 ...
Page 142: ...4 Electrical wiring 128 SMGB0087 rev 0 12 2013 4 7 8 RAS 4 6 HNC1E 3N 400V 50Hz XEK01265_4 ...
Page 146: ...4 Electrical wiring 132 SMGB0087 rev 0 12 2013 4 7 12 RAS 12HN P C 3N 400V 50Hz 7T146440 ...
Page 148: ......
Page 204: ......
Page 220: ......
Page 332: ......
Page 353: ...9 Spare parts 339 SMGB0087 rev 0 12 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211D ...
Page 362: ......
Page 484: ......
Page 496: ......
Page 497: ......