3 Piping work and
refrigerant charge
87
SMGB0087 rev.0 - 12/2013
3
Step 2: Additional refrigerant charge calculation for indoor unit (W
2
(kg))
When the outdoor unit is combined with indoor units RPI-(8/10)HP allowed (1 unit system combination only), it´s necessary
an additional refrigerant charge (W
2
) = 1kg/unit. For indoor units lower than 8 HP, an additional refrigerant charge it’s not
needed.
Indoor unit capacity
Additional refrigerant charge (W
2
(kg))
≥ 8 HP
1
< 8 HP
0
Step 3: Calculation of total additional refrigerant charge (W (kg))
a.
For all UTOPIA units except RAS-(8-12)HN(P/C)(E)
Put weight W
1
and W
2
calculated in step 1 and step 2 into the following formula:
W = W
1
+ W
2
System example (W) =
+
=
kg
b.
For UTOPIA units RAS-(8-12)HN(P/C)(E)
In case of RAS-(8-12)HN(P/C)(E), it must be used the following formula:
W = W
1
+ W
2
- C
System example (W) =
+
–
=
kg
C: Compensation value (kg) (Refer to the following table)
Model
Compensation value (C (kg))
RAS-8HN(P/C)E
1.6
RAS-10HN(P/C)E
2.0
RAS-12HN(P/C)
2.0
C A U T I O N
Do not exceed the allowed maximum additional charge
Step 4: Charging work
Charge refrigerant (R410A) into the system according to the instructions in the Service Manual.
Step 5: Total refrigerant charge of the system (W
TOT
(kg))
The total refrigerant charge of this system is calculated by the following formula:
W
TOT
= W + W
0
System example (W
TOT
) =
+
=
kg
W
0
is the outdoor unit refrigerant charge before shipment previous explained, and it’s shown in its specific table.
Finally, record the refrigerant charge quantity in order to facilitate maintenance and servicing activities.
Total additional charge W
kg
kg
Total ref. charge of this system
Date of ref. charge work
Year
Month
Day
Summary of Contents for RAS-(2-6)HVNP1(E)
Page 2: ......
Page 4: ... II ...
Page 28: ......
Page 134: ...4 Electrical wiring 120 SMGB0087 rev 0 12 2013 4 7 3 RAS 3HVNP1E 1 230V 50Hz XEK01261_0 ...
Page 136: ...4 Electrical wiring 122 SMGB0087 rev 0 12 2013 4 7 4 RAS 4 6 HVNP1E 1 230V 50Hz XEK01262_1 ...
Page 138: ...4 Electrical wiring 124 SMGB0087 rev 0 12 2013 4 7 6 RAS 4 6 HNP1E 3N 400V 50Hz XEK01263_2 ...
Page 140: ...4 Electrical wiring 126 SMGB0087 rev 0 12 2013 4 7 7 RAS 4 6 HVNC1E 1 230V 50Hz XEK01264_4 ...
Page 142: ...4 Electrical wiring 128 SMGB0087 rev 0 12 2013 4 7 8 RAS 4 6 HNC1E 3N 400V 50Hz XEK01265_4 ...
Page 146: ...4 Electrical wiring 132 SMGB0087 rev 0 12 2013 4 7 12 RAS 12HN P C 3N 400V 50Hz 7T146440 ...
Page 148: ......
Page 204: ......
Page 220: ......
Page 332: ......
Page 353: ...9 Spare parts 339 SMGB0087 rev 0 12 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211D ...
Page 362: ......
Page 484: ......
Page 496: ......
Page 497: ......