8 Troubleshooting
289
SMGB0087 rev.0 - 12/2013
8
Checking procedure of PCB by means of the Remote Control Switch
(1) Press and hold “ ” (menu) and “?” (help) simultaneously for 3
seconds during the normal mode.
The check menu is displayed.
Check Menu
Self Checking
02
/
02
I. U./O. U. PCB Check
ENT.
RTN.
SEL.
OK
(2) Select “I.U./O.U. PCB Check” from the check menu and press
“OK”.
(3) Select the set indoor unit by pressing “ ” and press “OK”.
(This screen is NOT displayed when the number of indoor units
connected with the remote control switch is 1 (one). In this case,
(4) will be displayed.)
I.U./O.U. PCB Check
01-01
02-01
03-01
04-01
04-02
04-03
04-04
03-02
03-03
03-04
01-02
02-02
02-03
02-04
01-03
01-04
RTN.
SEL.
OK
ENT.
(4) The indoor unit PCB and the outdoor unit PCB checks are started.
* If “ “ (menu) is pressed during the check, the check is canceled and
the screen will return to (2).
* If “ “ (return) is pressed during the check, the check is canceled
and the screen will return to (3).
Check 1: Checking
Check 2: Checking
Check 3: Checking
I.U./O.U. PCB: Check 01-01
(5) After completing the check, the result of PCB check will be indi-
cated. Press “ ” (return) and return to (3).
Check 1: 00
Check 2: 00
Check 3: 00
I.U./O.U. PCB: Check 01-01
Result of check table
Indoor Unit PCB
Outdoor Unit PCB
00
Normal
00
Normal
01
Abnormality of Inlet Air Temperature Thermistor
07
Abnormality of Transmission of Outdoor Unit
02
Abnormality of Outlet Air Temperature Thermistor
4
ITO Input Failure
03
Abnormality of Liquid Pipe Temperature Thermistor
5
PSH Input Failure
04
Abnormality of Remote Thermistor
6
Abnormality of Protection Signal Detection Circuit
05
Abnormality of Gas Pipe Temperature Thermistor
7
Abnormality of Phase Detection
01
Abnormality of Transmission of Central Station
8
Abnormality of Transmission of Inverter
08
Abnormality of EEPROM
A
Abnormality of High Pressure Sensor
0A
Zero Cross Input Failure
b
Abnormality of Compressor Discharge Gas Temperature Thermis-
tor
b
Abnormality of Transmission of I.U. during Check
C
Abnormality of Low Pressure Sensor
d
Abnormality of Evaporating Temperature Thermistor at Heating
Abnormality of Ambient Air Temperature Thermistor
Summary of Contents for RAS-(2-6)HVNP1(E)
Page 2: ......
Page 4: ... II ...
Page 28: ......
Page 134: ...4 Electrical wiring 120 SMGB0087 rev 0 12 2013 4 7 3 RAS 3HVNP1E 1 230V 50Hz XEK01261_0 ...
Page 136: ...4 Electrical wiring 122 SMGB0087 rev 0 12 2013 4 7 4 RAS 4 6 HVNP1E 1 230V 50Hz XEK01262_1 ...
Page 138: ...4 Electrical wiring 124 SMGB0087 rev 0 12 2013 4 7 6 RAS 4 6 HNP1E 3N 400V 50Hz XEK01263_2 ...
Page 140: ...4 Electrical wiring 126 SMGB0087 rev 0 12 2013 4 7 7 RAS 4 6 HVNC1E 1 230V 50Hz XEK01264_4 ...
Page 142: ...4 Electrical wiring 128 SMGB0087 rev 0 12 2013 4 7 8 RAS 4 6 HNC1E 3N 400V 50Hz XEK01265_4 ...
Page 146: ...4 Electrical wiring 132 SMGB0087 rev 0 12 2013 4 7 12 RAS 12HN P C 3N 400V 50Hz 7T146440 ...
Page 148: ......
Page 204: ......
Page 220: ......
Page 332: ......
Page 353: ...9 Spare parts 339 SMGB0087 rev 0 12 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211D ...
Page 362: ......
Page 484: ......
Page 496: ......
Page 497: ......