SMGB0087 rev.0 - 12/2013
Slo (Fan Speed) defrost setting (
bJ
)
Press “PSW1” and select the setting condition “1” at the slow defrost setting “
bJ
“.
Indoor fan operation is stopped during the defrost operation.
Setting condition
Indoor fan operation
0
Indoor fan stop during defrost operation
1
Indoor fan SLo during defrost operation
Cancellation of outdoor hot start limit (
H
)
Press “PSW1” and select the setting condition “1” at the cancellation of hot start setting “
H
”, so the hot start protection
control can be canceled.
Long piping setting (
nU
)
Press “PSW1” and select the setting condition “1” at the long piping setting “
nU
”.
If cooling capacity or heating capacity is not enough under the long-distance piping condition, this function can be set the
target compressor frequency higher than normal target value.
Compressor Frequency Control Target Value for Cooling (Control Function “
Hc
”)
Press “PSW1” and select the setting condition “1” in Compressor Frequency Control Target Value for Cooling “ ”. By set-
ting this function, the maximum compressor frequency and the target compressor frequency can be set higher than usual.
However, the maximum compressor frequency does not increase depending on the models.
Compressor Frequency Control Target Value for Heating (Control Function “
Hh
”)
Press “PSW1” and select the setting condition “1” in Compressor Frequency Control Target Value for Heating “ ”. By set-
ting this function, the maximum compressor frequency and the target compressor frequency can be set higher than usual.
However, the maximum compressor frequency does not increase depending on the models.
Indoor Expansion Valve Opening during Heating Operation Stoppage (Control Function “
5i
”)
Press “PSW1” and select the setting condition “1” or “2” in Indoor Expansion Valve Opening during Heating Operation
Stoppage “ ”. This function is utilized to change the indoor expansion valve opening during heating operation stoppage.
Indoor Expansion Valve Opening during Heating Thermo-OFF (Control Function “
5o
”)
Press “PSW1” and select the setting condition “1” or “2” in Indoor Expansion Valve Opening during Heating Thermo-OFF “
”. This function is utilized to change the indoor expansion valve opening during heating Thermo-OFF.
Indoor Expansion Valve Initial Opening at Start of Heating Operation (Control Function “
ci
”)
Press “PSW1” and select the setting condition “1” or “2” in Indoor Expansion Valve Initial Opening at Start of Heating Op-
eration “ ”. This function is utilized to change the indoor expansion valve initial opening at the start of heating operation.
Low Noise Setting (Control Function “
db
”)
Press “PSW1” and select the setting condition “0” to “3” in Low Noise Setting “ ”. Unlike Night-Shift, the maximum compres-
sor speed (for cooling and heating operation) can be set lower than usual regardless of the outdoor ambient temperature.
While this function is set, cooling or heating capacity also decreases to 80, 70, and 60% depending on the setting.
Maximum Compressor Frequency
Outdoor
Unit (HP)
Cooling Operation
Heating Operation
% Speed
db
= 0
db
= 1
db
= 2
db
= 3
db
= 0
db
= 1
db
= 2
db
= 3
100%
80%
70%
60%
100%
80%
70%
60%
Summary of Contents for RAS-(2-6)HVNP1(E)
Page 2: ......
Page 4: ... II ...
Page 28: ......
Page 134: ...4 Electrical wiring 120 SMGB0087 rev 0 12 2013 4 7 3 RAS 3HVNP1E 1 230V 50Hz XEK01261_0 ...
Page 136: ...4 Electrical wiring 122 SMGB0087 rev 0 12 2013 4 7 4 RAS 4 6 HVNP1E 1 230V 50Hz XEK01262_1 ...
Page 138: ...4 Electrical wiring 124 SMGB0087 rev 0 12 2013 4 7 6 RAS 4 6 HNP1E 3N 400V 50Hz XEK01263_2 ...
Page 140: ...4 Electrical wiring 126 SMGB0087 rev 0 12 2013 4 7 7 RAS 4 6 HVNC1E 1 230V 50Hz XEK01264_4 ...
Page 142: ...4 Electrical wiring 128 SMGB0087 rev 0 12 2013 4 7 8 RAS 4 6 HNC1E 3N 400V 50Hz XEK01265_4 ...
Page 146: ...4 Electrical wiring 132 SMGB0087 rev 0 12 2013 4 7 12 RAS 12HN P C 3N 400V 50Hz 7T146440 ...
Page 148: ......
Page 204: ......
Page 220: ......
Page 332: ......
Page 353: ...9 Spare parts 339 SMGB0087 rev 0 12 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211D ...
Page 362: ......
Page 484: ......
Page 496: ......
Page 497: ......