![Hitachi RAS-(2-6)HVNP1(E) Service Manual Download Page 420](http://html.mh-extra.com/html/hitachi/ras-2-6-hvnp1-e/ras-2-6-hvnp1-e_service-manual_2139503420.webp)
10 Servicing
406
SMGB0087 rev.0 - 12/2013
10.6.10 Removing reversing and solenoid valves coils
1
Remove the service cover following
“10.6.1 Removing service cover”
in this chapter.
2
Remove the connectors on the control PCB (PCB1) of the electrical box according to the following picture.
3
Remove the valve coils by removing 1 fixing screw for each coil.
Hold the coil of the
SVA and pull out
upward
Reversing valve coil
Hold the coil of the
reversing valve and pull
out to the right
Hold the coil of
the SVF and pull
out upward
Fixing screws
Rear cover
Upper cover
Electrical box
Hold the coil
of the SVC
and pull out
upward
P view
Fixing screw
4
When reassembling, perform the procedure in the reverse way of removing.
N O T E
Fix the wires by plastic bands to the original position.
10.6.11 Removing electronic expansion valve coil
1
Remove the service cover, the bottom service cover and the rear
cover following
“10.6.1 Removing service cover”
and
“10.6.4 Re-
moving the bottom service cover and rear cover”
.
2
Open the P plate turning counter clockwise approximately 90°.
• Check that the LED201 (red) on Inverter is OFF when the P
plate is opened.
3
Disconnect the CN5A connector on the control PCB1 of the
electrical box. Hold the coil of the expansion valve and pull out
upward. It is easier to remove the expansion valve coil if it is
rotated while pulling it upward.
4
When reassembling after replacing the expansion valve coil, per-
form the procedure in the reverse way of removing. The expan-
sion valve coil is equipped with a lock mechanism. After attaching
the expansion valve coil, rotate it until the sound of locking is
heard.
N O T E
Fix the wires by plastic bands to the original position.
Hold the coil of
the expansion
valve and pull
out upward
Expansion valve coil
Release lock
Summary of Contents for RAS-(2-6)HVNP1(E)
Page 2: ......
Page 4: ... II ...
Page 28: ......
Page 134: ...4 Electrical wiring 120 SMGB0087 rev 0 12 2013 4 7 3 RAS 3HVNP1E 1 230V 50Hz XEK01261_0 ...
Page 136: ...4 Electrical wiring 122 SMGB0087 rev 0 12 2013 4 7 4 RAS 4 6 HVNP1E 1 230V 50Hz XEK01262_1 ...
Page 138: ...4 Electrical wiring 124 SMGB0087 rev 0 12 2013 4 7 6 RAS 4 6 HNP1E 3N 400V 50Hz XEK01263_2 ...
Page 140: ...4 Electrical wiring 126 SMGB0087 rev 0 12 2013 4 7 7 RAS 4 6 HVNC1E 1 230V 50Hz XEK01264_4 ...
Page 142: ...4 Electrical wiring 128 SMGB0087 rev 0 12 2013 4 7 8 RAS 4 6 HNC1E 3N 400V 50Hz XEK01265_4 ...
Page 146: ...4 Electrical wiring 132 SMGB0087 rev 0 12 2013 4 7 12 RAS 12HN P C 3N 400V 50Hz 7T146440 ...
Page 148: ......
Page 204: ......
Page 220: ......
Page 332: ......
Page 353: ...9 Spare parts 339 SMGB0087 rev 0 12 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211D ...
Page 362: ......
Page 484: ......
Page 496: ......
Page 497: ......