3 Piping work and
refrigerant charge
74
SMGB0087 rev.0 - 12/2013
IVX Standard series
(m)
Outdoor Unit
3HP
4HP
5HP
6HP
8HP
10HP
12HP
Maximum piping length bet-
ween the outdoor unit and the
farthest indoor unit
Actual Length (L)
50
70
75
100
Equivalent Length (EL)
70
90
95
125
Total piping length
2 units (A+B+C)
60
80
85
100
115
3 units (A+B+C+D)
--
90
95
100
130
4 units
(A+B+C+D+E+F+G+)
--
90
95
100
145
Maximum piping line after first
branch
2 and 3 units (B, C, D)
10
15
4 units
(B+D, B+E, C+F, C+G)
--
10
15
Main piping length A
A > B, C, D, E, F, G
Maximum height difference Outdoor / Indoor (H)
(Outdoor Unit is Higher / Lower)
30 / 20
Maximum height difference Indoor / Indoor
3
Maximum height difference:
branch pipe/Indoor (2,3 and 4 indoor units system)
branch pipe/branch pipe (4 indoor units system)
3
Maximum lenth difference of the several branches:
(B-C) (2 and 3 unit system)
(B-D) (3 unit system)
(C-D) (3 unit system)
(C+G)-(C+F) (4 unit system)
(B+E)-(B+D) (4 unit system)
(C+G)-(B+E) (4 unit system)
(C+G)-(B+D) (4 unit system)
(C+F)-(B+E) (4 unit system)
(C+F)-(B+D) (4 unit system)
< 8
N O T E
• The liquid piping and the gas piping must be of the same piping length and run along the same route.
• Install the branch piping as much as possible near the indoor units.
• Install Multikits at the same horizontal level.
Summary of Contents for RAS-(2-6)HVNP1(E)
Page 2: ......
Page 4: ... II ...
Page 28: ......
Page 134: ...4 Electrical wiring 120 SMGB0087 rev 0 12 2013 4 7 3 RAS 3HVNP1E 1 230V 50Hz XEK01261_0 ...
Page 136: ...4 Electrical wiring 122 SMGB0087 rev 0 12 2013 4 7 4 RAS 4 6 HVNP1E 1 230V 50Hz XEK01262_1 ...
Page 138: ...4 Electrical wiring 124 SMGB0087 rev 0 12 2013 4 7 6 RAS 4 6 HNP1E 3N 400V 50Hz XEK01263_2 ...
Page 140: ...4 Electrical wiring 126 SMGB0087 rev 0 12 2013 4 7 7 RAS 4 6 HVNC1E 1 230V 50Hz XEK01264_4 ...
Page 142: ...4 Electrical wiring 128 SMGB0087 rev 0 12 2013 4 7 8 RAS 4 6 HNC1E 3N 400V 50Hz XEK01265_4 ...
Page 146: ...4 Electrical wiring 132 SMGB0087 rev 0 12 2013 4 7 12 RAS 12HN P C 3N 400V 50Hz 7T146440 ...
Page 148: ......
Page 204: ......
Page 220: ......
Page 332: ......
Page 353: ...9 Spare parts 339 SMGB0087 rev 0 12 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211D ...
Page 362: ......
Page 484: ......
Page 496: ......
Page 497: ......