![Hitachi RAS-(2-6)HVNP1(E) Service Manual Download Page 262](http://html.mh-extra.com/html/hitachi/ras-2-6-hvnp1-e/ras-2-6-hvnp1-e_service-manual_2139503262.webp)
8 Troubleshooting
248
SMGB0087 rev.0 - 12/2013
Alarm code
21
Abnormality of High pressure sensor for RAS-(3-12)H(V)NP(1)(E)
• The RUN LED flickers and “ALARM” is displayed on the remote control switch.
• The unit number, the alarm code and the unit code are alternately displayed on the set temperature section.
The unit number and the alarm code are displayed on the display of the outdoor unit PCB.
-
This alarm code is indicated when the pressure sensor output voltage decreases (less than 0.1V) or increases
(more than 4.9V) during the operation.
Is there connection problem of
CN7 on OU PCB1?
Connect correctly
Yes
No
Is 12V applied between number
1 and 3 of the connector CN7 on
OU PCB1?
Faulty OU PCB1
No
Yes
Abnormality of high
pressure sensor
Yes
Is voltage under 0.1V or over
4.9V between number 2 and 3 of
the connector CN7 on OU PCB1?
Faulty OU PCB1
No
Phenomenon
Cause
Check item
Action
(Turn OFF Main Switch)
Faulty top of compressor
thermistor
Fault
Check resistance
Replace thermistor if faulty
Incorrect connection
Check wiring to PCB1
Repair wiring and connections
Faulty PCB1
Replace PCB1 and check
operation
Replace PCB1 if faulty
Indication of pressure value is
excessively high or low
Malfunction of pressure sensor
due to clogging wiring
Replace pressure sensor
Summary of Contents for RAS-(2-6)HVNP1(E)
Page 2: ......
Page 4: ... II ...
Page 28: ......
Page 134: ...4 Electrical wiring 120 SMGB0087 rev 0 12 2013 4 7 3 RAS 3HVNP1E 1 230V 50Hz XEK01261_0 ...
Page 136: ...4 Electrical wiring 122 SMGB0087 rev 0 12 2013 4 7 4 RAS 4 6 HVNP1E 1 230V 50Hz XEK01262_1 ...
Page 138: ...4 Electrical wiring 124 SMGB0087 rev 0 12 2013 4 7 6 RAS 4 6 HNP1E 3N 400V 50Hz XEK01263_2 ...
Page 140: ...4 Electrical wiring 126 SMGB0087 rev 0 12 2013 4 7 7 RAS 4 6 HVNC1E 1 230V 50Hz XEK01264_4 ...
Page 142: ...4 Electrical wiring 128 SMGB0087 rev 0 12 2013 4 7 8 RAS 4 6 HNC1E 3N 400V 50Hz XEK01265_4 ...
Page 146: ...4 Electrical wiring 132 SMGB0087 rev 0 12 2013 4 7 12 RAS 12HN P C 3N 400V 50Hz 7T146440 ...
Page 148: ......
Page 204: ......
Page 220: ......
Page 332: ......
Page 353: ...9 Spare parts 339 SMGB0087 rev 0 12 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211D ...
Page 362: ......
Page 484: ......
Page 496: ......
Page 497: ......