8 Troubleshooting
221
SMGB0087 rev.0 - 12/2013
8
Phenomenon
Cause
Check item
Action
(Turn OFF the main switch)
Activation of the
high-pressure
switch due to the
excessively high
discharge pressure
(PSH)
Insufficient Air Flow to the Heat Exchanger (Outdoor Heat Ex-
changer during the Cooling Process or Indoor Heat Exchanger
during the Heating Process)
Check the heat exchanger
for dust or for clogging
Remove the dust or the clog-
ging
Check the air filter for dust
Remove the dust
Check for any obstacles at
the inlet or the outlet of the
heat exchanger
Remove the obstacles
Check the service area
Secure service area
Check the speed (Outdoor
Fan: Cooling / Indoor Fan:
Heating)
Replace the fan motor if
faulty
Excessively High Temp. Air to the Indoor Unit
Calculate the heat load
Reduce the heat load or use
a bigger unit
Check for hot air near the
ceiling (Heating)
Provide good circulation
Check for short-circuited air
(Heating)
Remove the short-circuited air
Check for other heat source
Remove the heat source
Faulty High-Pressure
Switch
Faulty Pressure Switch
Measure the discharge
pressure. Check the conti-
nuity after the decrease of
the pressure
Replace the pressure switch
if faulty
Insufficient Contacting
Measure the resistance by
means of the tester
Fix the looseness. Replace
the connector
Incorrect Connection
Check the connections
Repair the connections
Overcharged refrigerant
Check the cycle operation
temp.
Charge the refrigerant cor-
rectly
Mixture of the non-condensate gas in the refrigerant cycle
Check the air temp. and the
pressure
Recharge the refrigerant after
the vacuum pumping
Clogging of the discharge piping
Check for clogging
Remove the clogging
Liquid line stop valve or gas line stop valve is not in operation
Check the stop valves
Fully Open the stop valves
Faulty magnetic
contactor switch
No power is supplied to the coil
Check connections
Set the connections properly.
No power at the A contact
Measure the resistance
using a tester
Replace the magnetic switch
if it is broken
Summary of Contents for RAS-(2-6)HVNP1(E)
Page 2: ......
Page 4: ... II ...
Page 28: ......
Page 134: ...4 Electrical wiring 120 SMGB0087 rev 0 12 2013 4 7 3 RAS 3HVNP1E 1 230V 50Hz XEK01261_0 ...
Page 136: ...4 Electrical wiring 122 SMGB0087 rev 0 12 2013 4 7 4 RAS 4 6 HVNP1E 1 230V 50Hz XEK01262_1 ...
Page 138: ...4 Electrical wiring 124 SMGB0087 rev 0 12 2013 4 7 6 RAS 4 6 HNP1E 3N 400V 50Hz XEK01263_2 ...
Page 140: ...4 Electrical wiring 126 SMGB0087 rev 0 12 2013 4 7 7 RAS 4 6 HVNC1E 1 230V 50Hz XEK01264_4 ...
Page 142: ...4 Electrical wiring 128 SMGB0087 rev 0 12 2013 4 7 8 RAS 4 6 HNC1E 3N 400V 50Hz XEK01265_4 ...
Page 146: ...4 Electrical wiring 132 SMGB0087 rev 0 12 2013 4 7 12 RAS 12HN P C 3N 400V 50Hz 7T146440 ...
Page 148: ......
Page 204: ......
Page 220: ......
Page 332: ......
Page 353: ...9 Spare parts 339 SMGB0087 rev 0 12 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211D ...
Page 362: ......
Page 484: ......
Page 496: ......
Page 497: ......