Alarm code
05
Code abnormal operation of picking up phase signal
-
This alarm is displayed when the main power source phase is reversely connected or one phase is not connected.
Correctly connect each
phase of the power source
Yes
Reverse phase connection
(Only 3 phases unit)
No
Yes
No
Correctly connect each
phase of the power source
Faulty PCB1 or other cause
(see below)
PCB1 is normal
PCB1 is normal
Single phase
and 3 phases
(Is there any phase which is
not connected)?
RAS-(2-6)HVN(P/C)1(E)
RAS-(4-12)HN(P/C)(1)(E)
Voltage for unit to
be suspended
Running voltage:
207 to 253V
Setting voltage:
Less than 187V
Voltage for unit to
be suspended
Running voltage:
342 to 456V
Setting voltage:
Less than 323V
Phenomenon
Cause
Check item
Action
(Turn OFF the main switch)
Activation of
reverse phase
sensor in the
outdoor unit
Reverse or single phase
Check it according to
the electrical wiring
Replacing wires, repair, tight-
ening screws or correct wiring
Faulty outdoor unit PCB
-
Replace PCB if faulty
Summary of Contents for RAS-(2-6)HVNP1(E)
Page 2: ......
Page 4: ... II ...
Page 28: ......
Page 134: ...4 Electrical wiring 120 SMGB0087 rev 0 12 2013 4 7 3 RAS 3HVNP1E 1 230V 50Hz XEK01261_0 ...
Page 136: ...4 Electrical wiring 122 SMGB0087 rev 0 12 2013 4 7 4 RAS 4 6 HVNP1E 1 230V 50Hz XEK01262_1 ...
Page 138: ...4 Electrical wiring 124 SMGB0087 rev 0 12 2013 4 7 6 RAS 4 6 HNP1E 3N 400V 50Hz XEK01263_2 ...
Page 140: ...4 Electrical wiring 126 SMGB0087 rev 0 12 2013 4 7 7 RAS 4 6 HVNC1E 1 230V 50Hz XEK01264_4 ...
Page 142: ...4 Electrical wiring 128 SMGB0087 rev 0 12 2013 4 7 8 RAS 4 6 HNC1E 3N 400V 50Hz XEK01265_4 ...
Page 146: ...4 Electrical wiring 132 SMGB0087 rev 0 12 2013 4 7 12 RAS 12HN P C 3N 400V 50Hz 7T146440 ...
Page 148: ......
Page 204: ......
Page 220: ......
Page 332: ......
Page 353: ...9 Spare parts 339 SMGB0087 rev 0 12 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211D ...
Page 362: ......
Page 484: ......
Page 496: ......
Page 497: ......