6 Optional functions
164
SMGB0087 rev.0 - 12/2013
6.1.2 Available optional external signals
The outdoor units have the following signals that are described in the following table.
These signals are set up through the PCB of the outdoor unit.
Input signals (CN1 and CN2)
RAS-(2-2.5)HVNP1 / RAS-3HVNC1
Ind.
Input signal
Application
0
No setting application
No setting
1
Fixing the heating mode
This signal allows to pre-fix the operation mode, in this case the
heating mode, independently of what the indoor unit requests. If the
indoor units request the oposite mode than the outdoor unit, the com-
pressor will not start. This is very useful to set up a unique operation
mode.
2
Fixing the cooling mode
This signal allows to pre-fix the operation mode, in this case the
cooling mode, independently of what the indoor unit requests. If the
indoor units request the oposite mode than the outdoor unit, the com-
pressor will not start. This is very useful for computer rooms where
the cooling mode is fixed throughout the year.
3
Demand thermo OFF
This signal allows to stop the compressor if it reaches a certain pow-
er as well as to put the indoor unit in Thermo-OFF. This is very useful
for installations with high power consumption.
4
Forced stoppage
This signal allows to control the stoppage of the compressor and the
fans of the indoor as well as outdoor units. This is very useful when
used with the alarm signals of the fire prevention systems.
5
Current control demand
60%
This signal allows to regulate current consumption and establish an
average consumption of 60% of the rate point. This is very useful for
installations that run 24 hours a day.
6
Current control demand
80%
This signal allows to regulate current consumption and establish an
average consumption of 80% of the rate point.This is very useful for
installations that run 24 hours a day.
7
Current control demand
100%
This signal allows to regulate current consumption and establish an
average consumption of 100% of the rate point. This is very useful
for installations that run 24 hours a day.
RAS-3HVNP1E / RAS-(4-6)H(V)NP1E / RAS-(8-12)HN(P/C)(1)(E)
Ind.
Input signal
Application
0
No setting application
No setting
1
Fixing the heating mode
This signal allows to pre-fix the operation mode, in this case the
heating mode, independently of what the indoor unit requests. If the
indoor units request the oposite mode than the outdoor unit, the com-
pressor will not start. This is very useful to set up a unique operation
mode.
2
Fixing the cooling mode
This signal allows to pre-fix the operation mode, in this case the
cooling mode, independently of what the indoor unit requests. If the
indoor units request the oposite mode than the outdoor unit, the com-
pressor will not start. This is very useful for computer rooms where
the cooling mode is fixed throughout the year.
3
Demand thermo OFF
This signal allows to stop the compressor if it reaches a certain
power as well as to put the indoor unit in Thermo-OFF. This is very
useful for installations with high power consumption. This signal is
only activated if function F1 has value 1.
4
No setting application
No setting
5
Forced stoppage
This signal allows to control the stoppage of the compressor and the
fans of the indoor as well as outdoor units. This is very useful when
used with the alarm signals of the fire prevention systems. This signal
is only activated if function F1 has value 1.
Summary of Contents for RAS-(2-6)HVNP1(E)
Page 2: ......
Page 4: ... II ...
Page 28: ......
Page 134: ...4 Electrical wiring 120 SMGB0087 rev 0 12 2013 4 7 3 RAS 3HVNP1E 1 230V 50Hz XEK01261_0 ...
Page 136: ...4 Electrical wiring 122 SMGB0087 rev 0 12 2013 4 7 4 RAS 4 6 HVNP1E 1 230V 50Hz XEK01262_1 ...
Page 138: ...4 Electrical wiring 124 SMGB0087 rev 0 12 2013 4 7 6 RAS 4 6 HNP1E 3N 400V 50Hz XEK01263_2 ...
Page 140: ...4 Electrical wiring 126 SMGB0087 rev 0 12 2013 4 7 7 RAS 4 6 HVNC1E 1 230V 50Hz XEK01264_4 ...
Page 142: ...4 Electrical wiring 128 SMGB0087 rev 0 12 2013 4 7 8 RAS 4 6 HNC1E 3N 400V 50Hz XEK01265_4 ...
Page 146: ...4 Electrical wiring 132 SMGB0087 rev 0 12 2013 4 7 12 RAS 12HN P C 3N 400V 50Hz 7T146440 ...
Page 148: ......
Page 204: ......
Page 220: ......
Page 332: ......
Page 353: ...9 Spare parts 339 SMGB0087 rev 0 12 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211D ...
Page 362: ......
Page 484: ......
Page 496: ......
Page 497: ......