8 Troubleshooting
215
SMGB0087 rev.0 - 12/2013
8
Phenomenon
Cause
Check item
Action
(Turn OFF the main switch)
Cooling or heating
process with an
abnormal sound
Foreign particles inside of the fan casing
Visually inspect it
Remove the foreign particles
Indoor unit fan runner is hitting the casing
Visually inspect it
Adjust the position of the fan
runner
Outdoor unit propeller fan is hitting the shroud Visually inspect it
Adjust the position of the
propeller fan
Abnormal sound from
the compressor
Faulty Installation
Check that each part is
tightly fixed
Tightly fix each part
Liquid refrigerant
compression
Adjust the suction gas
temperature and pressure
Ensure superheat
Wear or breakage of
the internal
compressor parts
Abnormal sound from the
inside of the compressor
Replace the compressor
No heating by the oil
heater
Check the resistance (oil
heater, fFuse)
Replace the oil heater or the
fuse
Humming sound from the magnetic conductor Check the surface of the
contacts
Replace the magnetic switch
Abnormal vibration of the cabinets
Check each fixing screw
Tightly fix each screw
Outdoor fan does not
operate when the
compressor operates
Obstacle at the outdoor fan
Check the obstacles
Remove the obstacles
Watching condition for the heating process
Wait for the switching of the
4-way valve (1 ~ 3 minutes)
If the 4-way valve does not
switch, check for insufficient
refrigerant
Indoor fan does not
operate when the
compressor operates
Discharge pressure does not increase higher
than 1.5 Mpa due to the insufficient refrigerant
Check the operation
pressure *5)
Add the refrigerant
Disconnected wiring for the indoor fan
Check the wiring
Connect the wiring correctly
N O T E
• *1): Refer to section
“Self-checking procedure of the remote control switch”
.
• *2): Refer to section
“Self-checking procedure of PCB by means of the Remote Control Switch”
.
• *3): Even if the remote control switches are normal, the compressor does not operate under the following conditions:
1. Indoor temperature is lower than 21ºC or outdoor temperature Is lower than -5ºC during the cooling process
(DB).
2. Indoor temperature is higher than 27ºC (DB) or outdoor temperature is higher than 15ºC (WB) during the heating
process.
3. When a cooling (or heating) process signal is given to the outdoor unit and a different mode as heating (or cool-
ing) process signal is given to the indoor units.
4. When an emergency stop signal is given to outdoor unit.
• *4): Refer to chapter
“3. Piping work and refrigerant charge”
.
• *5): Refer to chapter
“7. Test run”
.
Summary of Contents for RAS-(2-6)HVNP1(E)
Page 2: ......
Page 4: ... II ...
Page 28: ......
Page 134: ...4 Electrical wiring 120 SMGB0087 rev 0 12 2013 4 7 3 RAS 3HVNP1E 1 230V 50Hz XEK01261_0 ...
Page 136: ...4 Electrical wiring 122 SMGB0087 rev 0 12 2013 4 7 4 RAS 4 6 HVNP1E 1 230V 50Hz XEK01262_1 ...
Page 138: ...4 Electrical wiring 124 SMGB0087 rev 0 12 2013 4 7 6 RAS 4 6 HNP1E 3N 400V 50Hz XEK01263_2 ...
Page 140: ...4 Electrical wiring 126 SMGB0087 rev 0 12 2013 4 7 7 RAS 4 6 HVNC1E 1 230V 50Hz XEK01264_4 ...
Page 142: ...4 Electrical wiring 128 SMGB0087 rev 0 12 2013 4 7 8 RAS 4 6 HNC1E 3N 400V 50Hz XEK01265_4 ...
Page 146: ...4 Electrical wiring 132 SMGB0087 rev 0 12 2013 4 7 12 RAS 12HN P C 3N 400V 50Hz 7T146440 ...
Page 148: ......
Page 204: ......
Page 220: ......
Page 332: ......
Page 353: ...9 Spare parts 339 SMGB0087 rev 0 12 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211D ...
Page 362: ......
Page 484: ......
Page 496: ......
Page 497: ......