3.4 Viewing Harmonic Measured Values
76
The instrument allows you to set an upper limit value for the harmonic analysis order. One example of how
this setting can be used is to set a limit on the uppermost order during total harmonic distortion (THD) mea-
surement. The setting applies to all channels.
Example: To set the harmonic analysis order upper limit value to 13
3.4.3 Setting the Analysis Order Upper Limit
1
Press
.
2
Press
to display the settings
screen shown to the left.
3
Press
or
to set the upper
limit value for analysis.
The
HRM LIMIT
lamp will light up if you set a value
other than 50.
The harmonic level and content percentage displays will include data up to the 50th order, even if the upper
limit is set to a value other than 50.
4
Press
to exit the settings.
The instrument will return to the normal measure-
ment state.