3.9 Using a Current Sensor
106
Setting external current sensor input
This section describes how to set the type of current sensor being used, the instrument’s CT ratio, and the
measurement range. These settings can be configured separately for each wiring mode.
See:
"3.2.2 Selecting the Current Input Method" (p.42)
"3.2.9 Setting the VT and CT Ratio" (p.59)
The instrument cannot automatically detect or set the current sensor type or CT ratio. When
using a current sensor, you must manually set the current sensor type and CT ratio. If you
replace the sensor with another unit that has a different rating, you must reconfigure the cur-
rent sensor type and the instrument’s CT ratio.
• When the current sensor type is set to “Off,” input from the current direct input terminals is enabled, and
external current sensor input is ignored.
• The panel displays the current measurement ranges when using external current sensor input as 10 A, 20
A, and 50 A. When the auto-range setting is enabled, auto-range operation will use the 10 A, 20 A, and 50
A ranges.
• When using the 9660 Clamp on Sensor, only the 100 A range (shown as the 10 A range on the instru-
ment’s panel) can be used.
• When using a wiring mode other than 1P2W that combines multiple channels, the combined channels will
be forced to use the same current sensor type, CT ratio, and range. At this time, other channel settings will
be changed to reflect the settings in use by the channel with the smallest value.
Current sensor types and instrument CT ratio settings
Current sensor
Current sensor rating
TYPE
CT ratio
9661 Clamp on Sensor
500 A AC
1
10
9669 Clamp on Sensor
1000 A AC
1
20
9660 Clamp on Sensor
100 A AC
1
10
CT9667 Flexible Clamp on Sensor
500A /5000A
1
10/100
CT6862 AC/DC Current Sensor
50 A AC/DC
2
1 (OFF)
CT6863 AC/DC Current Sensor
200 A AC/DC
2
4
CT6865 AC/DC Current Sensor
1000 A AC/DC
2
20
9709 AC/DC Current Sensor
500 A AC/DC
2
10
9277 Universal Clamp on CT
20 A AC/DC
2
0.4
9278 Universal Clamp on CT
200 A AC/DC
2
4
9279 Universal Clamp on CT
500 A AC/DC
2
10
9272-10 Clamp on Sensor
20 A/200 A AC
2
0.4/4
When the measurement target’s current exceeds the optional current
sensor’s rating
Use an external CT.
Summary of Contents for PW3336-01
Page 2: ......
Page 6: ...Contents iv...
Page 16: ...Operating Precautions 10...
Page 32: ...1 4 Measurement Workflow 26...
Page 44: ...2 7 Turning Off the Instrument 38...
Page 181: ...5 6 Wiring Specifications 175 5 3 phase 4 wire 3P4W Current sensor...
Page 182: ...5 6 Wiring Specifications 176...
Page 199: ...Appendix 4 Dimensional Diagram A13 e g PW3337 03 Appendix 4 Dimensional Diagram Unit mm...
Page 200: ...Appendix 4 Dimensional Diagram A14...
Page 203: ......
Page 204: ......
Page 205: ......
Page 206: ......