Appendix 9 Definitions
A
18
Terminology
K Factor
Also called the multiplication factor, the K factor expresses the power loss
caused by harmonic currents in a transformer.
The formula for calculating K factor (KF) is:
k: Order of harmonic
Ik: Percentage of harmonic current relative to the fundamental current [%]
Higher-order harmonic currents have a greater influence on the K factor than
do lower-order harmonic currents.
The K factor is measured while the transformer is subjected to the maximum
circuit load.
If the measured K factor is larger than the multiplication ratio of the transformer
being used, the transformer should be replaced with one having a higher K
factor, or the load on the transformer must be reduced.
When replacing a transformer, the replacement should have a K factor one
rank higher than the K factor measured with the transformer being replaced.
Harmonic Phase
Angle and Har-
monic Phase Dif-
ference
The harmonic voltage phase angle and harmonic current phase angle are
based upon the phase of the fundamental component of the PLL source
(referenced to the PLL input, which is selected from U1 in this instrument).
The phase difference between each harmonic component and the
fundamental component is expressed as an angle (º), with a positive sign
signifying lagging phase (LAG) and a negative sign signifying leading phase
(LEAD).
The harmonic voltage-current phase difference expresses the difference
between the phase of each harmonic order voltage component and the phase
of each harmonic order current component for each channel, as an angle (º).
The sum is the total power factor of each harmonic order (calculated from the
total harmonic power and total harmonic reactive power) expressed as an
angle (°). When the harmonic voltage-current phase difference is between -90°
and +90°, the
power of that harmonic order is flowing toward the load (inflow).
When it is b90° and +180° or between -90° and -180°, the power of
that harmonic order is flowing away from the load (outflow).
KF
k
2
I
k
×
2
k
1
=
50
I
k
2
k
1
=
50
----------------------------------
=
0
°
90
°
-90
°
±
180
°
Harmonic Phase Angle
Voltage-Current Phase Difference
Outflow
Inflow
LEAD (Lead)
LAG (Lag)
Voltage-Current
Phase Angle
Summary of Contents for 3197
Page 1: ...3197 POWER QUALITY ANALYZER May 2012 Revised edition 7 3197A981 07 12 05H Instruction Manual ...
Page 2: ......
Page 8: ...Contents vi ...
Page 30: ...1 3 Measurement Flowchart 22 ...
Page 44: ...2 5 Internal Operating Status and Memory Usage 36 ...
Page 86: ...4 6 Initializing the Instrument System Reset 78 ...
Page 134: ...6 4 Viewing Recorded Data REVIEW State 126 ...
Page 176: ...9 4 Disposing of the Instrument 168 ...
Page 199: ......
Page 200: ...3197 POWER QUALITY ANALYZER May 2012 Revised edition 7 3197A981 07 12 05H Instruction Manual ...