![Hioki 3197 Instruction Manual Download Page 119](http://html.mh-extra.com/html/hioki/3197/3197_instruction-manual_2137178119.webp)
6.3 Viewing Anomalous Phenomena (EVENT screen)
111
6
Voltage Dip
• Detection Method
Detect Using Urms 1/2.
Set the threshold as a percentage of nominal volt-
age. When the rms voltage falls below the nega-
tive threshold, it is detected as an “EVENT IN
(onset)" event. Subsequently, when the voltage
rises back above the threshold (plus appropriate
hysteresis), it is detected as an “EVENT OUT
(recovery)” event.
• Recording Contents
Event list data, voltage/corrent waveforms, event
voltage fluctuation graph
• Event Data Format
EVENT IN (Onset): Event no., occurrence date,
occurrence time, event type, channel, IN
EVENT OUT (Recovery): Event no., occurrence
date, occurrence time, event type, channel, OUT,
residual voltage, continuation period
• Event Voltage Fluctuation Graph
Fluctuation graph of Urms from about 0.5 sec-
onds before detection to about 2.5 seconds after
detection
Interruption
• Detection Method
Detect using Urms 1/2. Set the threshold as a
percentage of nominal voltage.
When the rms voltage falls below the threshold, it
is detected as an “EVENT IN (onset)" event. Sub-
sequently, when the voltage rises back above the
threshold (plus appropriate hysteresis), it is
detected as an “EVENT OUT (recovery)” event.
• Recording Contents
Event list data, voltage/corrent waveforms, event
voltage fluctuation graph
• Event Data Format
EVENT IN (Onset): Event no., occurrence date,
occurrence time, event type, channel, IN
Event EVENT OUT (Recovery): Event no., occur-
rence date, occurrence time, event type, channel,
OUT, residual voltage, continuation period
• Event Voltage Fluctuation Graph
Fluctuation graph of Urms from about 0.5 sec-
onds before detection to about 2.5 seconds after
detection
Summary of Contents for 3197
Page 1: ...3197 POWER QUALITY ANALYZER May 2012 Revised edition 7 3197A981 07 12 05H Instruction Manual ...
Page 2: ......
Page 8: ...Contents vi ...
Page 30: ...1 3 Measurement Flowchart 22 ...
Page 44: ...2 5 Internal Operating Status and Memory Usage 36 ...
Page 86: ...4 6 Initializing the Instrument System Reset 78 ...
Page 134: ...6 4 Viewing Recorded Data REVIEW State 126 ...
Page 176: ...9 4 Disposing of the Instrument 168 ...
Page 199: ......
Page 200: ...3197 POWER QUALITY ANALYZER May 2012 Revised edition 7 3197A981 07 12 05H Instruction Manual ...