6.3 Viewing Anomalous Phenomena (EVENT screen)
112
Transient Overvoltage
• Detection Method
During each cycle, signals between 10 and 100
kHz are detected by comparator on any of three
voltage channels if their amplitude exceeds ±70.7
Vpeak.
Presence Detection
• Recording Contents
Event List data, voltage/current waveforms
• Event Data Format
• EVENT IN (On set):Event number, occurrence
date, occurrence time, Event type, IN
• EVENT OUT (Recovery):Event number, occur-
rence date, occurrence time, Event type, OUT,
duration
Note 1:
Only the presence or non-presence of transient ov-
ervoltage is detected.
Voltage and current waveforms at the time of event
detection can be displayed. However, the transient
overvoltage waveform itself (circled in the diagram)
cannot be displayed.
Note 2:
Transient overvoltage that occurs repeatedly will be
detected as IN/OUT events. A transient overvoltage
occurring even once during a 200 ms period will be
identified as an IN event. Subsequent occurrence
will be monitored every 200 ms and when it is no
longer detected, an OUT event will be identified.
Rms Current (used to detect inrush current)
• Calculation Method
Rms current is calculated separately at each half-
cycle on three current channels (Irms 1/2).
Summary of Contents for 3197
Page 1: ...3197 POWER QUALITY ANALYZER May 2012 Revised edition 7 3197A981 07 12 05H Instruction Manual ...
Page 2: ......
Page 8: ...Contents vi ...
Page 30: ...1 3 Measurement Flowchart 22 ...
Page 44: ...2 5 Internal Operating Status and Memory Usage 36 ...
Page 86: ...4 6 Initializing the Instrument System Reset 78 ...
Page 134: ...6 4 Viewing Recorded Data REVIEW State 126 ...
Page 176: ...9 4 Disposing of the Instrument 168 ...
Page 199: ......
Page 200: ...3197 POWER QUALITY ANALYZER May 2012 Revised edition 7 3197A981 07 12 05H Instruction Manual ...