Temperature manager
8
17
If there is no buffer in the system, then the MUST-temperature from the individual modules is determined and
to that an adjustable temp. increase is added. The highest of these temperatures is the boiler-MUST-
temperature. To this an adjustable hysteresis is added and the result is the boiler-END-temperature (see Fig.
8.4). Caution: Consider the set minimum requirement.
Fig. 8.4: Example temperature manager when operation without buffer
If a time mode is applied directly on the buffer, then the required buffer-top-temperature is set directly in the
time mode module. Now it must be distinguished again if the buffer-top-temperature is higher than the
adjusted buffer-bottom-MUST-temperature. In this case the required boiler temperature is the result of the
required buffer-bottom-MUST-tempe the adjusted temp. in the adjusted difference (see Fig.
8.5). In this is not the case, the required boiler temperature is the result of the required temperature + the
8.6). Caution: Consider the set minimum requirement.
Fig. 8.5: Example temperature manager when time mode with difference
Summary of Contents for firestar de Luxe 18
Page 1: ...OPERATING INSTRUCTIONS Log wood boiler firestar de Luxe 18 40 ...
Page 80: ...16 Annex 80 16 ANNEX 16 1 Additional boiler module Hydraulic recommendation 1 ...
Page 81: ...Annex 16 81 Hydraulic recommendation 2 ...
Page 82: ...16 Annex 82 16 2 Solar module Program 1 ...
Page 83: ...Annex 16 83 Program 2 ...
Page 84: ...16 Annex 84 Program 3 ...
Page 85: ...Annex 16 85 Program 4 ...
Page 86: ...16 Annex 86 Program 5 ...
Page 87: ...Annex 16 87 Program 6 ...
Page 88: ...17 Notes 88 17 NOTES ...
Page 89: ...Notes 17 89 ...