Fault reports and their corrections
10
67
No. Fault report
Cause of fault
Fault correction
038
Maintenance
when exceeding the set inspection
interval (1000 operating hours)
▪
Conduct maintenance according to
maintenance schedule
▪
Fault has to be receipted manually:
Settings
→
Code entry
▪
If code is already set
→
Settings
press
039
SERVICE
when exceeding the set inspection
interval (3000 operating hours)
Carry out boiler system maintenance
by authorised personnel
040
OVERHEAT
ADD.BOILER
This fault text occurs if additional
boiler temperature exceeds 92 °C
-
041
HEATING OFF
Boiler operation mode “HEATING
OFF” is activated
-
042
BLOCKING
PROTECTION
Blocking protection is active
-
043
TIMEOUT ADD.
BOILER
Additional boiler minimum flue gas
temperature wasn´t reached within 1
hour (operation mode:
automatic/burner)
Check additional boiler
044
LEGIONELLA
PROTECTION.
Tank thermal disinfection active;
Tank will be heated up to 75°C
-
045
CHIMNEY SWEEP.
MODE
Chimney sweep function active
(see chapter Chimney sweep function)
046
MOD.ERR EXT.
Communication error of CAN 2 to
external module
▪
Check module CAN connection
▪
Check module
▪
✆
- contracting party
047
MOD.ERR INT.
Communication error of CAN 1 to
external module
▪
Check module CAN connection
▪
Check module
▪
✆
- contracting party
048
MOD.ERR BOILER
Communication error to boiler
module
▪
Check module CAN connection
▪
Check module
▪
✆
- contracting party
049
DATAERROR
MEMORY EXTERNAL
Data adjustment error at external
module
✆
- contracting party
050
DATAERROR
MEMORY INTERNAL
Data adjustment error at internal
module
✆
- contracting party
051
DATAERROR
MEMORY BOILER
Data adjustment error at boiler
module
✆
- contracting party
053
ADDITIONAL FLUE
GAS SENSOR
Additional boiler flue gas
temperature out of range
▪
Check sensor, replace as necessary
▪
Check plug, replace as necessary
▪
Check wiring incl. connections,
replace as necessary
054
EXTERNAL SET
POINT
Ext. No Signal of external
requirement or control (if line
monitoring is active)
▪
Check external (additional) control
signal
▪
Check plug, replace as necessary
▪
Check wiring incl. connections,
replace as necessary
055
BACK FLOW SET
Back flow set temperature could not
be reached during operation
▪
Function check mixer with mixer
motor
▪
Function check pump
▪
Check sensor position
Summary of Contents for firestar de Luxe 18
Page 1: ...OPERATING INSTRUCTIONS Log wood boiler firestar de Luxe 18 40 ...
Page 80: ...16 Annex 80 16 ANNEX 16 1 Additional boiler module Hydraulic recommendation 1 ...
Page 81: ...Annex 16 81 Hydraulic recommendation 2 ...
Page 82: ...16 Annex 82 16 2 Solar module Program 1 ...
Page 83: ...Annex 16 83 Program 2 ...
Page 84: ...16 Annex 84 Program 3 ...
Page 85: ...Annex 16 85 Program 4 ...
Page 86: ...16 Annex 86 Program 5 ...
Page 87: ...Annex 16 87 Program 6 ...
Page 88: ...17 Notes 88 17 NOTES ...
Page 89: ...Notes 17 89 ...